Coordination of Protection Systems for Performance During Faults and Specific Training for Personnel Reliability Standards

Federal Register, Volume 82 Issue 227 (Tuesday, November 28, 2017)

Federal Register Volume 82, Number 227 (Tuesday, November 28, 2017)

Proposed Rules

Pages 56186-56192

From the Federal Register Online via the Government Publishing Office www.gpo.gov

FR Doc No: 2017-25586

=======================================================================

-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

Federal Energy Regulatory Commission

18 CFR Part 40

Docket No. RM16-22-000

Coordination of Protection Systems for Performance During Faults and Specific Training for Personnel Reliability Standards

AGENCY: Federal Energy Regulatory Commission, Department of Energy.

ACTION: Notice of proposed rulemaking.

-----------------------------------------------------------------------

SUMMARY: The Federal Energy Regulatory Commission (Commission) proposes to approve Reliability Standards PRC-027-1 (Coordination of Protection Systems for Performance During Faults) and PER-006-1 (Specific Training for Personnel) submitted by the North American Electric Reliability Corporation (NERC). The purpose of proposed Reliability Standard PRC-

027-1 is to maintain the coordination of protection systems installed to detect and isolate faults on bulk electric system elements, such that those protection systems operate in the intended sequence during faults. The purpose of proposed Reliability Standard PER-006-1 is to ensure that personnel are trained on specific topics essential to reliability to perform or support real-time operations of the bulk electric system. In addition, the Commission proposes to direct NERC to develop certain modifications to proposed Reliability Standard PRC-027-

  1. DATES: Comments are due January 29, 2018.

    ADDRESSES: Comments, identified by docket number, may be filed in the following ways:

    Electronic Filing through http://www.ferc.gov. Documents created electronically using word processing software should be filed in native applications or print-to-PDF format and not in a scanned format.

    Mail/Hand Delivery: Those unable to file electronically may mail or hand-deliver comments to: Federal Energy Regulatory Commission, Secretary of the Commission, 888 First Street NE., Washington, DC 20426.

    Instructions: For detailed instructions on submitting comments and additional information on the rulemaking process, see the Comment Procedures Section of this document.

    FOR FURTHER INFORMATION CONTACT:

    Juan Villar (Technical Information), Office of Electric Reliability, Division of Reliability Standards and Security, 888 First Street NE., Washington, DC 20426, Telephone: (772) 678-6496, Juan.Villar@ferc.gov.

    Alan Rukin (Legal Information), Office of the General Counsel, Federal Energy Regulatory Commission, 888 First Street NE., Washington, DC 20426, Telephone: (202) 502-8502, Alan.Rukin@ferc.gov.

    SUPPLEMENTARY INFORMATION: 1. Pursuant to section 215 of the Federal Power Act (FPA), the Commission proposes to approve proposed Reliability Standards PRC-027-1 (Coordination of Protection Systems for Performance During Faults) and PER-006-1 (Specific Training for Personnel), which were submitted for approval by the North American Electric Reliability Corporation (NERC), the Commission-certified Electric Reliability Organization (ERO).\1\ As discussed below, however, the Commission also proposes to direct NERC to modify proposed Reliability Standard PRC-027-1 to require an initial protection system coordination study to ensure that applicable entities will perform (or have performed), as a baseline, a study demonstrating proper coordination of its protection systems. We propose to direct NERC to submit the modified Reliability Standard for Commission approval within 12 months following the effective date of a final rule in this proceeding.

    ---------------------------------------------------------------------------

    \1\ 16 U.S.C. 824o.

    ---------------------------------------------------------------------------

  2. The Commission also proposes to approve the associated violation risk factors, violation severity levels, implementation plans, and effective dates proposed by NERC for Reliability Standards PRC-027-1 and PER-006-1. The Commission further proposes to approve the retirement of currently-effective Reliability Standard PRC-001-1.1(ii) (System Protection Coordination).\2\

    ---------------------------------------------------------------------------

    \2\ The Commission approved Reliability Standard PRC-001-1.1(ii) on May 29, 2015. North American Electric Reliability Corporation, 151 FERC 61,186 (2015).

    ---------------------------------------------------------------------------

  3. In addition, the Commission proposes to approve new and revised definitions submitted by NERC for incorporation in the NERC Glossary of Terms Used in NERC Reliability Standards (``NERC Glossary'') for the following terms: (1) ``protection system coordination study;'' (2) ``operational planning analysis;'' and (3) ``real-time assessment.''

    Page 56187

    1. Background

    1. Section 215 and Mandatory Reliability Standards

  4. Section 215 of the FPA requires a Commission-certified ERO to develop mandatory and enforceable Reliability Standards, subject to Commission review and approval.\3\ Once approved, the Reliability Standards may be enforced by the ERO subject to Commission oversight or by the Commission independently.\4\ In 2006, the Commission certified NERC as the ERO pursuant to section 215 of the FPA.\5\

    ---------------------------------------------------------------------------

    \3\ Id. 824o(c), (d).

    \4\ Id. 824o(e).

    \5\ North American Electric Reliability Corp., 116 FERC 61,062, order on reh'g and compliance, 117 FERC 61,126 (2006), order on compliance, 118 FERC 61,190, order on reh'g, 119 FERC 61,046 (2007), aff'd sub nom. Alcoa Inc. v. FERC, 564 F.3d 1342 (D.C. Cir. 2009).

    ---------------------------------------------------------------------------

    1. Order No. 693

  5. On March 16, 2007, the Commission issued Order No. 693, approving 83 of the 107 Reliability Standards filed by NERC, including Reliability Standard PRC-001-1.\6\ In addition, the Commission directed NERC to develop modifications to Reliability Standard PRC-001-1 that:

    ---------------------------------------------------------------------------

    \6\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693, FERC Stats. & Regs. 31,242, at PP 1433-1449, order on reh'g, Order No. 693-A, 120 FERC 61,053 (2007).

    (1) Correct the references for Requirements, and sic (2) include a requirement that upon the detection of failures in relays or protection system elements on the Bulk-Power System that threaten reliable operation, relevant transmission operators must be informed promptly, but within a specified period of time that is developed in the Reliability Standards development process, whereas generator operators must also promptly inform their transmission operators; and (3) clarifies that, after being informed of failures in relays or protection system elements that threaten reliability of the Bulk-

    Power System, transmission operators must carry out corrective control actions, i.e., return a system to a stable state that respects system requirements as soon as possible and no longer than 30 minutes after they receive notice of the failure.\7\

    ---------------------------------------------------------------------------

    \7\ Order No. 693, FERC Stats. & Regs. 31,242 at P 1449.

    ---------------------------------------------------------------------------

    1. NERC Petition and Proposed Reliability Standards PRC-027-1 and PER-

    006-1

  6. On September 2, 2016, NERC submitted a petition seeking Commission approval of proposed Reliability Standards PRC-027-1 and PER-006-1.\8\ NERC states that the proposed Reliability Standards, new and revised NERC Glossary terms, and the retirement of Reliability Standard PRC-001-1.1(ii) satisfy the Commission's criteria in Order No. 672 and are just, reasonable, not unduly discriminatory or preferential, and in the public interest.\9\ NERC explains that the intent of the proposed Reliability Standards and changes to the NERC Glossary are to maintain the coordination of protection systems installed to detect and isolate faults on bulk electric system elements and require registered entities to provide training to their relevant personnel on protection systems and remedial action schemes. NERC asserts that the proposed Reliability Standards are an improvement over currently-effective Reliability Standard PRC-001-1.1(ii) and will ensure that appropriate personnel are trained on protection systems and that protection systems are appropriately studied, coordinated, and monitored.

    ---------------------------------------------------------------------------

    \8\ Proposed Reliability Standards PRC-027-1 and PER-006-1 are not attached to this Notice of Proposed Rulemaking. The proposed Reliability Standards are available on the Commission's eLibrary document retrieval system in Docket No. RM16-22-000 and are posted on the NERC Web site, http://www.nerc.com.

    \9\ NERC Petition at 10.

    ---------------------------------------------------------------------------

  7. Proposed Reliability Standard PER-006-1

  8. NERC states that proposed Reliability Standard PER-006-1 requires generator operators to use a systematic approach to develop and implement training for dispatch personnel at centrally-located dispatch centers.\10\ NERC explains that proposed Reliability Standard PER-006-1 will also cover plant personnel who are responsible for real-

    time control of a generator. NERC maintains that it is appropriate to train plant personnel in the functionality of protection systems and remedial action schemes. NERC observes that proposed Reliability Standard PER-006-1 replaces the phrase ``purpose and limitations'' used in currently-effective Reliability Standard PRC-001-1(ii) with the phrase ``operational functionality'' to clearly identify the objective of the training.\11\ NERC also observes that proposed Reliability Standard PER-006-1 replaces the phrase ``applied in its area'' in Reliability Standard PRC-001-1.1(ii) with the phrase ``that affect the output of the generating facility(ies) it operates'' to properly tailor the scope of the required training. NERC notes that proposed Reliability Standard PER-006-1 does not specify a periodicity for the required training.

    ---------------------------------------------------------------------------

    \10\ Id. at 13.

    \11\ Id. at 15.

    ---------------------------------------------------------------------------

  9. Proposed Reliability Standard PRC-027-1

  10. NERC asserts that proposed Reliability Standard PRC-027-1:

    provides a clear set of Requirements that obligate entities to (1) implement a process for establishing and coordinating new or revised Protection System settings, and (2) periodically study Protection System settings that could be affected by incremental changes in Fault current to ensure the Protection Systems continue to operate in their intended sequence.\12\

    ---------------------------------------------------------------------------

    \12\ Id. at 26.

    According to NERC, proposed Reliability Standard PRC-027-1, Requirement R1 mandates that each transmission owner, generator owner, and distribution provider establish a process for developing new and revised protection system settings for bulk electric system elements.\13\

    ---------------------------------------------------------------------------

    \13\ Id. at 27.

    ---------------------------------------------------------------------------

  11. NERC states that proposed Reliability Standard PRC-027-1, Requirement R2 mandates that every six years, applicable entities must either: (1) Perform a protection system coordination study to determine whether the protection systems continue to operate in the intended sequence during faults; (2) compare present fault current values to an established fault current baseline and, only if the comparison identifies a 15 percent or greater deviation in fault current values (either three phase or phase to ground) at a bus to which the bulk electric system is connected, perform a protection system coordination study; or (3) use a combination of options 1 and 2.\14\

    ---------------------------------------------------------------------------

    \14\ Id. at 26.

    ---------------------------------------------------------------------------

  12. NERC explains that proposed Reliability Standard PRC-027-1, Requirement R3 will require applicable entities to use the process established under proposed Reliability Standard PRC-027-1, Requirement R1 for the development of any new or revised protection system settings.

  13. Proposed Retirement of Reliability Standard PRC-001-1.1(ii)

  14. NERC states that Reliability Standard PRC-001-1.1(ii) includes six requirements that are either addressed by Reliability Standards approved by the Commission or by the proposed Reliability Standards. Specifically, NERC explains that Reliability Standard PRC-001-1.1(ii), Requirement R1 has been partially replaced by currently-effective Reliability Standards PER-003-1 and PER-005-2. NERC continues that proposed Reliability Standard PER-006-1 and the proposed revised definitions of operational planning

    Page 56188

    analysis and real-time assessment will replace the remaining portions of Reliability Standard PRC-001-1.1(ii), Requirement R1. NERC asserts that Reliability Standard PRC-001-1.1(ii), Requirement R2 has been addressed by Reliability Standards IRO-001-4, IRO-008-2, IRO-010-2, TOP-001-3, and TOP-003-3, which the Commission approved in Order No. 817.\15\ NERC states that Reliability Standard PRC-001-1.1(ii), Requirements R3 and R4 will be replaced with proposed Reliability Standard PRC-027-1. NERC also explains that Reliability Standard PRC-

    001-1.1(ii), Requirement R5 has been replaced with several Reliability Standards developed after Reliability Standard PRC-001-1(ii) became effective.\16\ NERC further states that Reliability Standard PRC-001-

    1.1(ii), Requirement R6 has been replaced with Reliability Standards TOP-001-3 and TOP-003-3.

    ---------------------------------------------------------------------------

    \15\ Id. at 5 (citing Transmission Operations Reliability Standards and Interconnection Reliability Operations and Coordination Reliability Standards, Order No. 817, 153 FERC 61,178 (2015)).

    \16\ Id. at 6.

    ---------------------------------------------------------------------------

    1. Discussion

  15. Pursuant to section 215(d)(2) of the FPA, we propose to approve proposed Reliability Standards PER-006-1 and PRC-027-1 as just, reasonable, not unduly discriminatory or preferential, and in the public interest, as both proposed Reliability Standards improve upon currently-effective Reliability Standard PRC-001-1.1(ii) in important ways.\17\ Specifically, proposed Reliability Standard PRC-027-1 does so by (1) modifying the applicability section to include the appropriate functional entity types with the responsibilities, resources, and skill sets to conduct the studies required to coordinate protection systems, and (2) listing the protection system functions on all bulk electric system elements that require coordination. Proposed Reliability Standard PER-006-1, along with existing formal training requirements in the PER group of Reliability Standards, also improves upon Reliability Standard PRC-001-1.1(ii), Requirement R1 by ensuring that the necessary personnel are familiar with and understand the purpose and limitations of protection systems schemes while providing more precise and auditable requirements. However, proposed Reliability Standard PRC-027-

    1, Requirement R2, Option 2 does not appear to ensure coordination of all bulk electric system elements with protection system functions. Accordingly, pursuant to section 215(d)(5) of the FPA, we propose to direct that NERC develop modifications to proposed Reliability Standard PRC-027-1 that address our concern regarding this gap, as discussed below.

    ---------------------------------------------------------------------------

    \17\ 16 U.S.C. 824o(d)(2).

    ---------------------------------------------------------------------------

  16. In addition, we propose to approve NERC's associated violation risk factors, violation severity levels, implementation plans, and effective dates. We also propose to approve the revised definitions for inclusion in the NERC Glossary. Further, we propose to approve the retirement of Reliability Standard PRC-001-1.1(ii), as requested by NERC.

  17. Pursuant to 215(d)(5) of the FPA, we propose to direct that NERC develop modifications to proposed Reliability Standard PRC-027-1 addressing our concern that applicable entities that choose Requirement R2, Option 2 perform (or have already performed) an initial baseline study demonstrating proper coordination of their protection systems. Any additional protection system coordination studies would be necessary only if an applicable entity is confronted with 15 percent or greater fault current deviations from the prior baseline study amounts, as currently proposed in Reliability Standard PRC-027-1, Requirement R2, Option 2. We propose to direct NERC to submit the modified Reliability Standard within 12 months following the effective date of a final rule in this proceeding.

  18. Proposed Reliability Standard PRC-027-1, Requirement R2 does not require an initial protection system coordination study if an applicable entity elects Option 2. Unlike Option 1, which requires performance of protection system coordination studies every six years, Option 2 requires applicable entities to ``compare present Fault current values to an established Fault current baseline and perform a Protection System Coordination Study when the comparison identifies a 15 percent or greater deviation.'' The proposed Reliability Standard and NERC's petition do not indicate that the ``Fault current baseline'' must be established through an initial protection system coordination study. Instead, NERC's petition states that the baseline must be established ``by the effective date of the standard based on short-

    circuit studies.'' \18\ The proposed Reliability Standard provides that ``the initial Fault current baseline(s) shall be established by the effective date of this Reliability Standard and updated each time a Protection System Coordination Study is performed,'' but this language does not require establishing the ``initial Fault current baseline'' through an initial protection system coordination study.\19\ NERC's petition reinforces this understanding, as noted above, by explicitly allowing the use of short-circuit studies to establish the initial Fault current baseline.

    ---------------------------------------------------------------------------

    \18\ NERC Petition at 36 n.35.

    \19\ Proposed Reliability Standard PRC-027-1, Requirement R2, Option 2 n.1. Footnote 1 further states that if an ``initial baseline was not established by the effective date of this Reliability Standard because of the previous use of an alternate option or the installation of a new BES Element, the entity may establish the baseline by performing a Protection System Coordination Study'' (emphasis added). Id.

    ---------------------------------------------------------------------------

  19. While they are related terms, we understand there to be a difference between short-circuit studies and protection system coordination studies. NERC defines protection system coordination study as an ``analysis to determine whether Protection Systems operate in the intended sequence during Faults.'' \20\ By comparison, proposed Reliability Standard PRC-027-1 explains that a short-circuit study is ``an analysis of an electrical network that determines the magnitude of the currents flowing in the network during an electrical fault . . . and are used as the basis for protection device coordination studies.'' \21\ Therefore, while short-circuit studies are inputs to protection system coordination studies, it appears that a short-circuit study differs in scope from a protection system coordination study. Based on this record, it would be incorrect to conclude that proposed Reliability Standard PRC-027-1, Requirement R2, Options 1 and 2 afford the same level of protection system coordination because the former requires a protection system coordination study while the latter does not.

    ---------------------------------------------------------------------------

    \20\ NERC Petition, Exhibit A-3, Proposed Definitions. This definition is consistent with the definition of coordination of protection in IEEE Std. C37.113-1999 (stating that the ``process of choosing settings or time delay characteristics of protective devices, such that operation of the devices will occur in a specified order to minimize customer service interruption and power system isolation due to a power system disturbance'').

    \21\ Proposed Reliability Standard PRC-027-1, Supplemental Material at 8.

    ---------------------------------------------------------------------------

  20. While we generally support permitting flexibility in the Reliability Standards to achieve required performance goals, the possibility that some bulk electric system elements may never undergo a protection system coordination study raises reliability concerns. In past serious Bulk-Power System events, mis-coordination was a contributing factor to misoperations and outages. For example, the Arizona Southern California September 8, 2011 Outage Report identified an instance

    Page 56189

    where a transmission owner did not perform a protection system coordination study prior to the implementation of a protection system.\22\ The 2011 Outage Report stated that this omission negatively affected the reliable operation of the Bulk-Power System during the 2011 event.\23\

    ---------------------------------------------------------------------------

    \22\ Arizona Southern California September 8, 2011 Outage Report at 101-103, https://www.ferc.gov/legal/staff-reports/04-27-2012-ferc-nerc-report.pdf.

    \23\ Id. at 100-102.

    ---------------------------------------------------------------------------

  21. Over the past eleven years, several NERC reports have addressed the importance of protection system coordination to Bulk-Power System reliability. Proposed Reliability Standard PRC-027-1 addresses some of the issues raised in these reports; but without requiring an initial protection system coordination study, the proposed Reliability Standard does not address all of them. In 2006, for example, the NERC System Protection Control Task Force assessed Reliability Standard PRC-

  22. \24\ The report recommended requiring the coordination of all existing protection systems.\25\

    ---------------------------------------------------------------------------

    \24\ NERC SPCTF Assessment of Standard PRC-001-0--System Protection Coordination (2006), http://www.nerc.com/pa/Stand/Project200706SystemProtectionCoordinationDL/NERC_SPCTF_Assessment_of_Standard_PRC.pdf.

    \25\ Id. at 3-4.

    ---------------------------------------------------------------------------

  23. In 2009, in a letter from the NERC President to the NERC Board of Trustees and stakeholders, NERC identified generation and transmission mis-coordination as responsible for 30 percent of the misoperations that occurred between 2005 and 2008.\26\ The 2009 letter stated that mis-coordination between generation and transmission protection systems ``has caused two significant system disturbances in the past two years, and resulted in the unnecessary loss of generation during seven additional disturbances in that timeframe.'' \27\ The letter explained that the 2009 NERC System Protection Initiative would initially focus on the area of protection system coordination.\28\

    ---------------------------------------------------------------------------

    \26\ NERC Letter from Rick Sergel, NERC President, Regarding System Protection Initiative at Figure 2 (April 24, 2009).

    \27\ Id. at 1.

    \28\ Id. at 1-2.

    ---------------------------------------------------------------------------

  24. In 2013, NERC issued a Misoperations Report prepared by the Protection System Misoperations Task Force.\29\ The Misoperations Report identified ``ways to potentially reduce the amount of future misoperations'' and concluded that ``misoperations due to setting errors can potentially be reduced.'' \30\ The identified techniques to reduce incorrect settings, included: Peer reviews, increased training, more extensive fault studies, standard templates for setting standard schemes using complex relays, and periodic review of existing settings when there is a change in system topography.\31\ In the ReliabilityFirst region, NERC identified a category of misoperations caused by ``Engineering/Design Issues,'' which specifically included setting mis-coordination.\32\ This category of misoperations was one of the three most common causes of misoperations for above 200 kV facilities within the ReliabilityFirst region.\33\ The positive impact on Bulk-Power System reliability of reducing misoperations because of ``Incorrect setting/logic/design errors'' is found in NERC's 2015 Analysis of System Protection Misoperations:

    ---------------------------------------------------------------------------

    \29\ NERC Misoperations Report (2013), http://www.nerc.com/comm/PC/Protection%20System%20Misoperations%20Task%20Force%20PSMTF%202/PSMTF_Report.pdf.

    \30\ Id. at 3.

    \31\ Id.

    \32\ Id. at 14-15. The 2013 Misoperations Report elaborated that the ``Engineering/Design Issues'' category included:

    Incorrect short circuit values and coordination errors. The incorrect short circuit values included outdated or incorrect data used to calculate relay settings. The coordination errors in these cases all involved pilot protection either of insufficient carrier blocking trip delays or of improper choice of ground pickup values used in a blocking scheme. Id. at 15.

    \33\ Id. at 14.

    The State of Reliability 2015 report found that protection system misoperations continued to be a significant contributor to automatic transmission outage severity. In general, transmission system events with protection system misoperations were more impactful than other transmission events. They were also a significant contributor to transmission outage severity, indicating that a reduction in protection system misoperations would lead to an improvement in system reliability.\34\

    ---------------------------------------------------------------------------

    \34\ NERC, Analysis of System Protection Misoperations at 1 (Dec. 2015) (citations omitted), http://www.nerc.com/pa/RAPA/PA/Performance%20Analysis%20DL/2015_Analysis_of_System_Protection_Misoperations_Final.pdf (finding that 31 percent of all misoperations were due to ``Incorrect setting/logic/design errors'').

  25. In 2014, a NERC ``lessons learned'' document on ``Generation Relaying--Underfrequency Protection Coordination'' identified a 2014 incident where underfrequency relay trip settings were installed on the system unnecessarily and were not coordinated with a generator's relay trip setting.\35\ The document explained that ``unintended generator tripping during an underfrequency event can exacerbate the condition.'' \36\ The document also stated that ``generator relay protection should be coordinated with all auxiliary power system relaying with specific regard to time-delay settings'' in order to ensure reliable generator operation.\37\

    ---------------------------------------------------------------------------

    \35\ NERC, Lesson Learned, Generation Relaying--Underfrequency Protection Coordination (2014), http://www.nerc.com/pa/rrm/ea/Lessons%20Learned%20Document%20Library/LL20140601_Generation_Relaying_Underfrequency_Protection_Coordination_final.pdf.

    \36\ Id.

    \37\ Id.

    ---------------------------------------------------------------------------

  26. The 2016 State of Reliability Report noted that while protection system misoperations declined in 2015, misoperations showed a ``statistically significant positive correlation with transmission outage severity and showed a higher relative transmission risk.'' \38\ Misoperations showed the strongest correlation of the factors considered. In addition, the 2016 State of Reliability Report identified that ``over 40 percent of the incorrect setting/logic/design misoperations were due to the miss coordination sic of ground overcurrent settings'' found by ERCOT.\39\

    ---------------------------------------------------------------------------

    \38\ 2016 State of Reliability Report at 17, http://www.nerc.com/pa/RAPA/Pages/default.aspx.

    \39\ Id. at 166.

    ---------------------------------------------------------------------------

  27. The 2017 State of Reliability Report recognized the significance of protection system misoperations to Bulk-Power System reliability by observing that ``protection system misoperations should remain an area of focus as it continues to be one of the largest contributors to the severity of transmission outages.'' \40\

    ---------------------------------------------------------------------------

    \40\ 2017 State of Reliability Report at 2.

    ---------------------------------------------------------------------------

  28. For the reasons discussed above, we propose to direct that NERC develop modifications to proposed Reliability Standard PRC-027-1 to address our concern by requiring that applicable entities perform an initial protection coordination study under Requirement R2, Option 2. We propose that applicable entities would have six years from the effective date of a modified Reliability Standard to complete the analysis. An applicable entity could use pre-existing protection system coordination studies to satisfy the proposed requirement provided it was reasonable (i.e., no intervening system changes that would render the earlier work obsolete). After conducting the initial protection system coordination study, subsequent protection system coordination studies would only be required when an applicable entity is confronted with 15 percent or greater fault current deviations from the prior baseline study amounts, as currently proposed in Reliability Standard PRC-027-1, Requirement R2, Option 2. We seek comments on this proposal.

  29. Separately, we seek comment from NERC and other interested entities explaining the technical basis for

    Page 56190

    employing a 15 percent deviation threshold in proposed Reliability Standard PRC-027-1, Requirement R2, Option 2. We seek to better understand the basis for this threshold to ensure an adequate record in the proceeding on this matter.

    1. Information Collection Statement

  30. The collection of information addressed in this Notice of Proposed Rulemaking is subject to review by the Office of Management and Budget (OMB) under section 3507(d) of the Paperwork Reduction Act of 1995.\41\ OMB's regulations require approval of certain information collection requirements imposed by agency rules.\42\ Upon approval of a collection(s) of information, OMB will assign an OMB control number and an expiration date. Respondents subject to the filing requirements of a rule will not be penalized for failing to respond to these collections of information unless the collections of information display a valid OMB control number.

    ---------------------------------------------------------------------------

    \41\ 44 U.S.C. 3507(d).

    \42\ 5 CFR 1320.11.

    ---------------------------------------------------------------------------

  31. The Commission will submit the information collection requirement to OMB for its final review and approval. We solicit public comments on the need for this information, whether the information will have practical utility, the accuracy of the burden estimates, ways to enhance the quality, utility, and clarity of the information to be collected or retained, and any suggested methods for minimizing respondents' burden, including the use of automated information techniques.

  32. The information collection requirements in this Notice of Proposed Rulemaking in Docket No. RM16-22-000 are associated with FERC-

    725A,\43\ FERC-725G6,\44\ and FERC-725Y, as discussed below.

    ---------------------------------------------------------------------------

    \43\ FERC-725A (OMB Control No. 1902-0244) currently includes the information collection requirements associated with Reliability Standard PRC-001-1.1(ii), which is proposed for retirement. Only one item per OMB Control No. may be pending OMB review at a time, and an unrelated item affecting FERC-725A is pending OMB review. We are providing estimates of the burden reduction related to FERC-725A for review and comment. However, to submit this Notice of Proposed Rulemaking timely to OMB, the Commission is being conservative and not reducing the burden estimates associated with FERC-725A at this time.

    \44\ The information collection requirements related to proposed Reliability Standard PRC-027-1 would normally be included in FERC-

    725G (OMB Control No. 1902-0252). However, only one item per OMB Control No. may be pending OMB review at a time, and an unrelated item affecting FERC-725G is pending OMB review. For this Notice of Proposed Rulemaking and the related submittal to OMB, we use a placeholder information collection no. of FERC-725G6.

    ---------------------------------------------------------------------------

  33. Public Reporting Burden: The number of respondents below is based on an examination of the NERC compliance registry on April 7, 2017, for transmission owners, generator owners, generator operators, and distribution providers within the United States and an estimate of how many entities from that registry will be affected by the Reliability Standards proposed for adoption and implementation. At the time of Commission review of proposed Reliability Standards PRC-027-1 and PER-006-1, 334 transmission owners, 913 generator owners, 875 generator operators, and 365 distribution providers in the United States were registered in the NERC compliance registry. However, under NERC's compliance registration program, entities may be registered for multiple functions, so these numbers incorporate some double counting. We note that many generation sites share a common generator owner or generator operator. The following table provides the estimated proposed annual burden and cost related to information collection requirements in this Notice of Proposed Rulemaking.\45\

    ---------------------------------------------------------------------------

    \45\ TO = transmission owner; TOP = transmission operator; GO = generator owner; GOP = generator operator; DP = distribution provider; and BA = balancing authority.

    Proposed Changes in the NOPR in Docket No. RM16-22-000

    ----------------------------------------------------------------------------------------------------------------

    Annual

    number of Total number Average burden Annual burden

    Respondent category and Number of responses of annual hours and cost hours and total

    requirement \46\ respondents per responses per response \47\ annual cost

    respondent (rounded) \48\

    (1) (2) (1) * (2) = (4)............... (3) * (4) = (5)

    (3)

    ----------------------------------------------------------------------------------------------------------------

    FERC-725G6 (Covering Proposed Reliability Standard PRC-027-1) \49\

    ----------------------------------------------------------------------------------------------------------------

    TO; Reporting Reqs. R1, R2, & 334 1 334 60 hrs.; $3,941.40 20,040 hrs.;

    R3. $1,316,428.

    TO; Recordkeeping Reqs......... 334 1 334 40 hrs.; $1,565.60 13,360 hrs.;

    $522,910.

    GO; Reporting Reqs. R1, R2, & 913 1 913 10 hrs.; $656.90.. 9,130 hrs.;

    R3. $599,750.

    GO; Recordkeeping Reqs......... 913 1 913 10 hrs.; $391.40.. 9,130 hrs.;

    $357,348.

    DP; Reporting Reqs R1, R2, & R3 365 1 365 10 hrs.; $656.90.. 3,650 hrs.;

    $239,769.

    DP; Recordkeeping Reqs......... 365 1 365 10 hrs.; $391.40.. 3,650 hrs.;

    $142,861.

    ------------------

    Sub-Total for Reporting ............ ............ ............ .................. 32,820 hrs.;

    Reqs. for FERC-725G6. $2,155,947.

    Sub-Total for Recordkeeping ............ ............ ............ .................. 26,140 hrs.;

    Reqs. for FERC-725G6. $1,023,119.

    ------------------

    Total Proposed Increase ............ ............ ............ .................. 58,960 hrs.;

    for FERC-725G6. $3,179,066.

    ----------------------------------------------------------------------------------------------------------------

    FERC-725Y (Covering Proposed Reliability Standard PER-006-1)

    ----------------------------------------------------------------------------------------------------------------

    GOP; Reporting Req. R1......... 875 1 875 5 hrs.; $328.45... 4,375 hrs.;

    $287,394.

    GOP; Recordkeeping Req......... 875 1 875 10 hrs.; $391.40.. 8,750 hrs.;

    $342,475.

    Total Proposed Increase for ............ ............ ............ .................. 13,125 hrs.;

    FERC-725Y. $629,869.

    ----------------------------------------------------------------------------------------------------------------

    Reductions to FERC-725A (Covering Proposed Retirement of Reliability Standard PRC-001-1.1) \50\

    ----------------------------------------------------------------------------------------------------------------

    GOP; Reporting Req............. 875 1 875 40 hrs.; $2,627.60 35,000 hrs.;

    $2,299,150.

    GOP; Recordkeeping Req......... 875 1 875 50 hrs.; $1,957.00 43,750 hrs.;

    $1,712,375.

    Page 56191

    TOP; Reporting Req............. 177 1 177 60 hrs.; $3,941.40 10,620 hrs.;

    $697,628.

    TOP; Recordkeeping Req......... 177 1 177 70 hrs.; $2,739.80 12,390 hrs.;

    $484,945.

    BA; Reporting Req.............. 99 1 99 32 hrs.; $2,102.08 3,168 hrs.;

    $208,106.

    BA; Recordkeeping Req.......... 99 1 99 20 hrs.; $782.80.. 1,980 hrs.;

    $77,497.

    Reduction Sub-Total ............ ............ ............ .................. 48,788 hrs.;

    Reporting Reqs. for FERC- $3,204,884.

    725A.

    ------------------

    Reduction Sub-Total ............ ............ ............ .................. 58,120 hrs.;

    Recordkeeping Reqs. for $2,274,817.

    FERC-725A.

    ------------------

    Reduction, Sub-Total for ............ ............ ............ .................. 106,908 hrs.;

    FERC-725A. $5,479,701

    (reduction).

    ------------------

    NET TOTAL REDUCTION FOR ............ ............ ............ .................. 34,823 hrs.;

    PROPOSED CHANGES IN $1,670,766

    NOPR IN RM16-22-000. (reduction).

    ----------------------------------------------------------------------------------------------------------------

    Titles: FERC-725G6 (Mandatory Reliability Standard PRC-027-1) and FERC-725Y (Mandatory Reliability Standards: Operations Personnel Training (PER-005-2 and PER-006-1).

    ---------------------------------------------------------------------------

    \46\ For each Reliability Standard, the Measure shows the acceptable evidence for the associated Reporting Requirement, and the Compliance section details the related Recordkeeping Requirement.

    \47\ Based on data from the Bureau of Labor Statistics, the average hourly cost (wages plus benefits) is $65.69/hour for an engineer, and $39.14/hour for a record clerk. The hourly cost for an engineer is used for reporting requirements; the hourly cost for a record clerk is used for recordkeeping requirements.

    \48\ For display purposes, the cost figures in column 5 have been rounded.

    \49\ Some of the reporting requirements are required at least every six calendar years. In this table, the Commission assumes that respondents might work on some of their elements each year; the annual burden estimate shown is one sixth of the burden associated with one complete six-year cycle. For example, for each transmission owner: (a) the annual reporting burden associated with Requirements R1, R2, and R3 is shown as 60 hours per year, and (b) the burden for the six-year cycle would be six times that, or a total of 360 hours.

    \50\ The estimates for average annual burden hours per response are based on Order No. 693, FERC Stats. & Regs. 31,242 at PP 1906, 1907. The numbers of respondents and estimated hourly costs are based on current figures.

    ---------------------------------------------------------------------------

    Action: Revision to existing collections and proposed new information collection.

    OMB Control Nos.: To be determined (FERC-725G6) \51\ and 1902-0279 (FERC-725Y).

    ---------------------------------------------------------------------------

    \51\ OMB will assign a Control No. when it issues a decision.

    ---------------------------------------------------------------------------

    Respondents: Business or other for profit, and not for profit institutions.

    Frequency of Responses: Annual recordkeeping and reporting requirements, with some reporting requirements being at least once every six years.

    Necessity of the Information: Proposed Reliability Standards PRC-

    027-1 and PER-006-1 set forth requirements for coordination of protection systems and personnel training on specific topics essential to reliability. The Commission proposes to approve proposed Reliability Standards PRC-027-1 and PER-006-1, which will replace Commission-

    approved Reliability Standard PRC-001-1.1(ii). The proposed Reliability Standards PRC-027-1 and PER-006-1 improve upon the existing Reliability Standard PRC-001-1.1(ii) because the proposed Reliability Standards assign responsibilities to entities with more appropriate resources and skill sets to conduct studies required to coordinate protection systems. The proposed Reliability Standards also provide additional clarity to the applicable entities.

    Internal review: The Commission has assured itself, by means of its internal review, that there is specific, objective support for the burden estimates associated with the information requirements.

  34. Interested persons may obtain information on the reporting requirements by contacting the Federal Energy Regulatory Commission, Office of the Executive Director, 888 First Street NE., Washington, DC 20426 Attention: Ellen Brown, email: DataClearance@ferc.gov, phone: (202) 502-8663, fax: (202) 273-0873.

  35. Comments concerning the information collection proposed in this Notice of Proposed Rulemaking and the associated burden estimates should be sent to the Commission in this docket and may also be sent to the Office of Management and Budget, Office of Information and Regulatory Affairs Attention: Desk Officer for the Federal Energy Regulatory Commission. For security reasons, comments should be sent by email to OMB at the following email address: oira_submission@omb.eop.gov. Please refer to OMB Control Nos. to be determined (FERC-725G6) and 1902-0279 (FERC-725Y) in your submittal.

    1. Environmental Analysis

  36. The Commission is required to prepare an Environmental Assessment or an Environmental Impact Statement for any action that may have a significant adverse effect on the human environment.\52\ The action proposed here falls within the categorical exclusion in the Commission's regulations for rules that are clarifying, corrective or procedural, for information gathering, analysis, and dissemination.\53\

    ---------------------------------------------------------------------------

    \52\ Regulations Implementing the National Environmental Policy Act of 1969, Order No. 486, FERC Stats. & Regs. 30,783 (1987) (cross-referenced at 41 FERC 61,284).

    \53\ 18 CFR 380.4(a)(2)(ii).

    ---------------------------------------------------------------------------

    1. Regulatory Flexibility Act

  37. The Regulatory Flexibility Act of 1980 (RFA) generally requires a description and analysis of proposed rules that will have significant economic impact on a substantial number of small entities.\54\ The Small Business Administration (SBA) defines

    Page 56192

    which utilities are small businesses based on the number of employees that a utility and its affiliates employ.\55\

    ---------------------------------------------------------------------------

    \54\ 5 U.S.C. 601-612.

    \55\ 13 CFR 121.201, Subsector 221.

    ---------------------------------------------------------------------------

  38. The proposed Reliability Standard PRC-027-1 (included in FERC-

    725G6) will apply to approximately 1,612 entities (334 transmission owners, 913 generator owners, and 365 distribution providers) in the United States.\56\ Pursuant to SBA regulations, the employment threshold for transmission is 500 employees, for generator owners is between 250 and 750 employees (depending on the fuel source), and for distribution providers is 1,000 employees. We estimate that the annual cost for each entity will be $1,048 for each generator owner and distribution provider and $5,507 for each transmission owner.

    ---------------------------------------------------------------------------

    \56\ Many respondents serve multiple roles in the NERC compliance registry, so there is likely double counting in the estimates.

    ---------------------------------------------------------------------------

  39. The proposed Reliability Standard PER-006-1 (included in FERC-

    725Y) will apply to approximately 875 generator operators in the United States. Pursuant to SBA regulations the employment threshold for generator operators is between 250 and 750 employees (depending on the fuel source). We estimate that the annual cost for each generator operator will be $719.

  40. In addition, this Notice of Proposed Rulemaking proposes the retirement of Reliability Standard PRC-001-1.1(ii) (included in FERC-

    725A). That retirement would decrease the annual estimated cost for 875 generator operators by $4,585 each, for 177 transmission operators by $6,681 each, and for 99 balancing authorities by $2,885 each. For the generator operators affected by this retirement and the proposed Reliability Standard PER-006-1, the net annual effect would be a decrease of $3,866 each. We estimate the net annual cost of this Notice of Proposed Rulemaking would vary, by type of entity, from an annual decrease of $6,681 (for each transmission operator) to an annual increase of $5,507 (for each transmission owner). We view this as a minimal economic impact for each entity. Accordingly, we certify that the proposed Reliability Standards PRC-027-1 and PER-006-1 and retirement of Reliability Standard PRC-001-1.1 (ii) will not have a significant economic impact on a substantial number of small entities.

    1. Comment Procedures

  41. The Commission invites interested persons to submit comments on the matters and issues proposed in this notice to be adopted, including any related matters or alternative proposals that commenters may wish to discuss. Comments are due January 29, 2018. Comments must refer to Docket No. RM16-22-000, and must include the commenter's name, the organization they represent, if applicable, and their address in their comments.

  42. The Commission encourages comments to be filed electronically via the eFiling link on the Commission's Web site at http://www.ferc.gov. The Commission accepts most standard word processing formats. Documents created electronically using word processing software should be filed in native applications or print-to-PDF format and not in a scanned format. Commenters filing electronically do not need to make a paper filing.

  43. Commenters that are not able to file comments electronically must send an original of their comments to: Federal Energy Regulatory Commission, Secretary of the Commission, 888 First Street NE., Washington, DC 20426.

  44. All comments will be placed in the Commission's public files and may be viewed, printed, or downloaded remotely as described in the Document Availability section below. Commenters on this proposal are not required to serve copies of their comments on other commenters.

    1. Document Availability

  45. In addition to publishing the full text of this document in the Federal Register, the Commission provides all interested persons an opportunity to view and/or print the contents of this document via the Internet through the Commission's Home Page (http://www.ferc.gov) and in the Commission's Public Reference Room during normal business hours (8:30 a.m. to 5:00 p.m. Eastern time) at 888 First Street NE., Room 2A, Washington, DC 20426.

  46. From the Commission's Home Page on the Internet, this information is available on eLibrary. The full text of this document is available on eLibrary in PDF and Microsoft Word format for viewing, printing, and/or downloading. To access this document in eLibrary, type the docket number of this document, excluding the last three digits, in the docket number field.

  47. User assistance is available for eLibrary and the Commission's Web site during normal business hours from the Commission's Online Support at (202) 502-6652 (toll free at 1-866-208-3676) or email at ferconlinesupport@ferc.gov, or the Public Reference Room at (202) 502-

    8371, TTY (202) 502-8659. Email the Public Reference Room at public.referenceroom@ferc.gov.

    By direction of the Commission.

    Issued November 16, 2017.

    Nathaniel J. Davis, Sr.,

    Deputy Secretary.

    FR Doc. 2017-25586 Filed 11-27-17; 8:45 am

    BILLING CODE 6717-01-P

VLEX uses login cookies to provide you with a better browsing experience. If you click on 'Accept' or continue browsing this site we consider that you accept our cookie policy. ACCEPT