Energy conservation: Commercial and industrial equipment; energy efficiency program— Commercial heating, air-conditioning, and water heating equipment standards,

[Federal Register: March 7, 2007 (Volume 72, Number 44)]

[Rules and Regulations]

[Page 10038-10049]

From the Federal Register Online via GPO Access [wais.access.gpo.gov]

[DOCID:fr07mr07-3]

DEPARTMENT OF ENERGY

Office of Energy Efficiency and Renewable Energy

10 CFR Part 431

[Docket Nos. EE-RM/STD-03-100, EE-RM/STD-03-200, and EE-RM/STD-03-300]

RIN Nos. 1904-AB16, 1904-AB17, and 1904-AB44

Energy Efficiency Program for Certain Commercial and Industrial Equipment: Efficiency Standards for Commercial Heating, Air- Conditioning, and Water-Heating Equipment

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of Energy.

ACTION: Final rule.

SUMMARY: The Energy Policy and Conservation Act, as amended (EPCA), establishes energy conservation standards for various commercial and industrial equipment. EPCA further provides with respect to certain equipment covered by this rule, that if the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) and the Illuminating Engineering Society of North America (IESNA) amend ASHRAE/ IESNA Standard 90.1 as in effect on October 24, 1992, then the Department of Energy (DOE) must establish amended national standards at the ASHRAE/IESNA Standard 90-1 minimum energy efficiency levels unless DOE determines that evidence supports adoption of higher standard levels or certain other circumstances exist. ASHRAE/IESNA amended ASHRAE/IESNA Standard 90.1 on October 29, 1999 (ASHRAE/IESNA Standard 90.1-1999), and DOE initiated this rulemaking to consider amendments to the national standards. DOE has concluded that it lacks authority to pursue higher standards for gas-fired instantaneous water heaters and large commercial packaged boilers. For small commercial packaged boilers with capacities greater than 300,000 Btu/h and less than or equal to 2.5 million British thermal units per hour, DOE is declining to adopt revised efficiency standards contained in the ASHRAE/IESNA Standard 90.1-1999 because the revised levels are less stringent than the current national standard. In addition, DOE has decided to conduct a separate rulemaking to consider whether standards at higher levels than those in the ASHRAE/IESNA Standard 90.1-1999 are warranted for packaged terminal air conditioners and packaged terminal heat pumps. Finally, DOE has concluded it does not have the authority to adopt, as uniform national standards, efficiency standards contained in Addenda f and b, respectively, to ASHRAE/IESNA Standard 90.1-2004 for three-phase air conditioners and heat pumps with cooling capacities less than 65,000 British thermal units per hour, and single-package vertical air conditioners and single-package vertical heat pumps with cooling capacities less than 65,000 Btu/h.

DATES: Effective Date: April 6, 2007.

FOR FURTHER INFORMATION CONTACT: Maureen Murphy, Project Manager, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Program, EE-2J, 1000 Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-0598, or e-mail Maureen.Murphy@ee.doe.gov.

Francine Pinto, Esq., U.S. Department of Energy, Office of the General Counsel, GC-72, 1000 Independence Avenue, SW., Washington, DC 20585-0103, (202) 586-9507, or e-mail Francine.Pinto@hq.doe.gov.

SUPPLEMENTARY INFORMATION: I. Introduction

  1. Summary of Today's Actions

  2. Authority

  3. Background

    1. ASHRAE/IESNA Standard 90.1 and the Department of Energy's Response

    2. Subsequent Action by the Department of Energy

    3. The Energy Policy Act of 2005 II. Discussion of Comments and DOE Final Rule

  4. Large Commercial Packaged Boilers (Greater Than 2.5 million British Thermal Units Per Hour) and Gas-Fired Instantaneous Water Heaters

  5. Small Commercial Packaged Boilers (Greater Than 300,000 British Thermal Units Per Hour and Less Than or Equal to 2.5 million British Thermal Units Per Hour)

  6. Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps

  7. Three-Phase Air Conditioners and Heat Pumps less than 65,000 British Thermal Units Per Hour

  8. Single-Package Vertical Air Conditioners and Single-Package Vertical Heat Pumps Less Than 65,000 Btu/h

  9. Single-Package Vertical Air Conditioners and Single-Package Vertical Heat Pumps Greater Than or Equal to 65,000 Btu/h and Less Than 240,000 Btu/h III. Procedural Requirements

  10. Review Under Executive Order 12866

  11. Review Under the Regulatory Flexibility Act

  12. Review Under the Paperwork Reduction Act of 1995

  13. Review Under the National Environmental Policy Act of 1969

  14. Review Under Executive Order 13132

  15. Review Under Executive Order 12988

  16. Review Under the Unfunded Mandates Reform Act of 1995

  17. Review Under the Treasury and General Government Appropriations Act, 1999

    I. Review Under Executive Order 12630

  18. Review Under the Treasury and General Government Appropriations Act, 2001

  19. Review Under Executive Order 13211

    L. Congressional Notification IV. Approval of the Office of the Secretary

    I. Introduction

  20. Summary of Today's Actions

    Today's final rule addresses five categories of commercial equipment \1\: (1) Small and large commercial packaged boilers; (2) gas-fired instantaneous water heaters; (3) packaged terminal air conditioners (PTACs) and packaged terminal heat pumps (PTHPs); (4) three-phase air conditioners (ACs) and heat pumps (HPs) with cooling capacities less than 65,000 British thermal units per hour (Btu/h); and (5) single-package vertical air conditioners (SPVAC) and single-package vertical heat pumps (SPVHP), collectively referred to as single package vertical units (SPVUs).

    \1\ DOE uses the terms ``product'' and ``equipment'' interchangeably in this final rule. Where DOE refers to the categories of ``residential products'' covered by 10 CFR Part 430, DOE uses the phrase ``residential products.''

    By today's action, DOE is publishing a final rule that prescribes no amended standard. As discussed in section II.A through II.F of this notice, DOE has decided:

    [[Page 10039]]

    (1) Not to amend the standards for large commercial packaged boilers (greater than 2.5 million Btu/h) and gas-fired instantaneous water heaters because ASHRAE/IESNA did not amend the levels for these products in ASHRAE/IESNA Standard 90.1-1999 and, thus, did not trigger the provision requiring DOE to amend the standards established under EPCA;

    (2) Not to amend the standards for small commercial packaged boilers (greater than 300,000 Btu/h and less than or equal to 2.5 million Btu/h) because the ASHRAE/IESNA Standard 90.1-1999 levels for these products are less stringent than the existing EPCA standards;

    (3) Not to amend the standards for packaged terminal air conditioners and packaged terminal heat pumps because DOE will conduct a separate rulemaking to determine if clear and convincing evidence supports standard levels higher than those in ASHRAE/IESNA Standard 90.1-1999;

    (4) Not to amend the standards for three-phase air conditioners and heat pumps less than 65,000 Btu/h because EPACT 2005 amended EPCA to provide that only an amendment to ASHRAE/IESNA Standard 90.1 as in effect on January 1, 2010, triggers DOE to amend the standards established under EPCA;

    (5) Not to amend the standards for single-package vertical air conditioners and single-package vertical heat pumps less than 65,000 Btu/h because EPACT 2005 amended EPCA to provide that only an amendment to ASHRAE/IESNA Standard 90.1 as in effect on January 1, 2010, triggers DOE to amend the standards established under EPCA; and

    (6) Not to amend the standards for single-package vertical air conditioners and single-package vertical heat pumps greater than or equal to 65,000 Btu/h and less than 240,000 Btu/h because DOE has determined that these products are covered by standards established by EPACT 2005 for large commercial package air conditioning and heating equipment with cooling capacities greater than or equal to 65,000 Btu/h and less than 760,000 Btu/h.

  21. Authority

    Part C of Title III of EPCA addresses the energy efficiency of certain types of commercial and industrial equipment. (42 U.S.C. 6311- 6317) It contains, for example, specific mandatory energy conservation standards for tankless, gas-fired IWHs; PTACs and PTHPs; small and large commercial packaged boilers; and commercial package air- conditioning and heating equipment. The latter category includes three- phase ACs and HPs with cooling capacities less than 65,000 Btu/h, as well as SPVACs and SPVHPs with cooling capacities less than 65,000 Btu/ h. (42 U.S.C. 6313(a)(1)-(5))

    The energy conservation standards set forth in EPCA for these and related types of commercial and industrial equipment generally correspond to the levels in ASHRAE/IESNA Standard 90.1, effective October 24, 1992 (ASHRAE/IES Standard 90.1-1989). Pursuant to section 342(a)(6)(A)(i) of EPCA, DOE, except in certain circumstances, must amend energy conservation standards for the listed ASHRAE equipment if ASHRAE amends ASHRAE/IESNA Standard 90.1. With respect to certain types of commercial and industrial equipment, including all of the equipment covered by today's rule, prior to the enactment of Energy Policy Act of 2005 (EPACT 2005), any amendment of ASHRAE/IES Standard 90.1, as in effect on October 24, 1992 (the date of enactment of the Energy Policy Act of 1992) would trigger DOE action for adopting amended uniform national standards for this equipment. EPACT 2005 changed the October 24, 1992, date for small and large commercial package air conditioning and heating equipment, so that only an amendment of ASHRAE/IES Standard 90.1 as in effect on January 1, 2010, would trigger DOE action to adopt amended uniform national standards. Pursuant to EPACT 2005, this provision also applies to ``very large'' commercial package air conditioning and heating equipment. Id. Any SPVU with a cooling capacity below 760,000 Btu/h would be within the definition of small, large, or very large commercial package air conditioning and heating equipment. (42 U.S.C. 6311(8)(A)-(D))

    Under certain circumstances delineated in EPCA, DOE may adopt standards more stringent than the levels in amendments to ASHRAE/IES Standard 90.1. (42 U.S.C. 6313(6)(A)(i)-(ii)) In any such rulemaking, the rule must contain the amended standard. The Secretary may not prescribe any amended standard that increases maximum allowable energy use, or decreases the minimum required energy efficiency, of the covered equipment. (42 U.S.C. 6313(a)(6)(B)(ii)) Furthermore, the Secretary may not prescribe an amended standard if the Secretary publishes a finding that interested persons have established by a preponderance of evidence that the amended standard is likely to result in the unavailability in the United States of products with performance characteristics (including reliability), features, sizes, capacities, and volumes that are substantially the same as those generally available in the United States at the time of the Secretary's finding. (42 U.S.C. 6313(a)(6)(B)(ii))

  22. Background

    1. ASHRAE/IESNA Standard 90.1 and the Department of Energy's Response \2\

    \2\ A more detailed discussion of the ASHRAE process can be found in DOE's Notice of Availability and request for public comment on this rulemaking published on March 13, 2006 in the Federal Register. 71 FR 12634.

    On October 29, 1999, ASHRAE approved and published ASHRAE/IESNA Standard 90.1-1999, which addressed efficiency levels for many categories of commercial heating, ventilating, air-conditioning (HVAC), and water-heating equipment covered by EPCA. ASHRAE/IESNA Standard 90.1-1999 revised the efficiency levels in ASHRAE/IESNA Standard 90.1- 1989 for certain equipment. For the remaining equipment, ASHRAE left the preexisting levels in place after considering revising the levels for some equipment and deferring consideration of others.

    Following publication of ASHRAE/IESNA Standard 90.1-1999, DOE performed a screening analysis for the categories of equipment for which ASHRAE addressed efficiency levels in ASHRAE/IESNA Standard 90.1, to determine what action DOE would take with respect to these levels. 65 FR 10984. Upon completion of the screening analysis, DOE published a notice of document availability and public workshop on May 15, 2000. The May 15, 2000, notice invited written comments on the screening analysis and DOE's planned actions and described the screening analysis and announced its availability to the public. 65 FR 30929. For each equipment category for which ASHRAE adopted or considered an amended efficiency level, the notice stated what action DOE was inclined to take. 65 FR 30935. ASHRAE did not amend the standard levels for three- phase ACs and HPs with cooling capacities less than 65,000 Btu/h at that time. However, it was DOE's understanding that the ASHRAE Standard 90.1 committee intended to amend the levels once the DOE rulemaking for residential central air conditioners energy efficiency standards had been completed. Based on ASHRAE's action and DOE's understanding of the ASHRAE Standard 90.1 committee's intention to adopt the same level as DOE adopted for residential central air conditioners, DOE stated that it had decided to take no action until ASHRAE had amended ASHRAE/IESNA Standard 90.1's

    [[Page 10040]]

    efficiency levels for three-phase ACs and HPs with cooling capacities less than 65,000 Btu/h. 71 FR 12643. In Addendum f to ASHRAE/IESNA Standard 90.1-2004, ASHRAE adopted the same minimum energy efficiency standards for this equipment as DOE had adopted for residential central air conditioners. ASHRAE adopted Addendum f to ASHRAE/IESNA Standard 90.1-2004 on April 1, 2006.

    Following the public meeting on July 11, 2000, DOE adopted the efficiency levels in ASHRAE/IESNA Standard 90.1-1999 as uniform national standards to replace existing EPCA levels for 18 categories of commercial equipment in the January 2001 final rule. 66 FR 3335, 3336- 37, 3349-52 (January 12, 2001). DOE also rejected the ASHRAE/IESNA Standard 90.1-1999 levels for electric water heaters, leaving the EPCA level in place for that equipment. 66 FR 3337.

    In this same final rule, for 11 categories of commercial equipment,\3\ DOE stated it would evaluate whether to adopt more stringent standards than those contained in ASHRAE/IESNA Standard 90.1- 1999. 66 FR 3336-38, 3349-52. For the four categories of three-phase air-conditioning equipment that ASHRAE had not addressed in ASHRAE/ IESNA Standard 90.1-1999, DOE understood that ASHRAE intended to amend its efficiency levels for this equipment in conjunction with the then- pending DOE standards rulemaking for similar, single-phase residential products.\4\ The standard levels prescribed in EPCA and ASHRAE/IESNA Standard 90.1-1999 for these 15 equipment categories \5\ appear in Tables I.1 and I.2. EPACT 2005 included energy efficiency standards for some of these commercial air conditioners and heat pumps; those new standards also appear in Tables I.1 and I.2. EPACT 2005 prescribed more stringent standards than those contained in ASHRAE/IESNA Standard 90.1- 1999 for commercial package air-conditioning and heating equipment with cooling capacities between 65,000 Btu/h and 240,000 Btu/h as listed in Table I.1.\6\

    \3\ These eleven products include small commercial package air- conditioning and heating equipment with capacities greater than or equal to 65,000 Btu/h and less than 135,000 Btu/h, large commercial package air-conditioning and heating equipment with capacities greater than or equal to 135,000 Btu/h and less than 240,000 Btu/h, packaged terminal air conditioners and heat pumps, small, gas-fired and oil-fired, commercial packaged boilers greater than 300,000 Btu/ h and less than or equal to 2,500,000 Btu/h, large, gas-fired and oil-fired, commercial packaged boilers greater than 2,500,000 Btu/h, and gas-fired instantaneous water heaters.

    \4\ The four categories of three-phase commercial air conditioners and air conditioning hear pumps are: Commercial three- phase, air-source, split-system air conditioners with cooling capacities less than 65,000 Btu/h, commercial three-phase, air- source, single split-system heat pumps with cooling capacities less than 65,000 Btu/h, commercial three-phase, air-source, single package air conditioners with cooling capacities less than 65,000 Btu/h, and commercial three-phase, air-source, single package heat pumps with cooling capacities less than 65,000 Btu/h.

    \5\ These fifteen products include the eleven products and four categories of commercial three-phase commercial air conditioners and air conditioning heat pumps identified above.

    \6\ SPVUs are specific types of small and large commercial package air-conditioning and heating equipment. ASHRAE did not recognize and evaluate them as separate equipment categories in ASHRAE/IESNA Standard 90.1-1999, nor did EPCA recognize them as separate equipment categories.

    Table I.1.--Energy Conservation Standards for Commercial Air Conditioners and Heat Pumps

    Standard efficiency level* Product

    Capacity/

    characteristics

    EPCA

    ASHRAE/IESNA standard 90.1-1999

    EPACT 2005

    Small Commercial Package Air-

    =65 kBtu/h and =65 kBtu/h and =135 kBtu/h and =135 kBtu/h and 300 kBtu/h

    Combustion Efficiency Thermal Efficiency \**\: and Gas-Fired

    2,500 kBtu/h

    Combustion Efficiency Combustion Efficiency \**\: \**\:

    Gas-Fired--80% Gas-Fired--80%

    Oil-Fired--83% Oil-Fired--83%

    Gas-Fired Instantaneous 2.5 MMBtu/h).

    standard level higher than those specified in ASHRAE/IESNA Standard 90.1- 1999. Three-Phase ACs and HPs

    Adopt Addendum f to ASHRAE/IESNA Standard (

VLEX uses login cookies to provide you with a better browsing experience. If you click on 'Accept' or continue browsing this site we consider that you accept our cookie policy. ACCEPT