Revisions to Modeling, Data, and Analysis Reliability Standard

Federal Register, Volume 78 Issue 145 (Monday, July 29, 2013)

Federal Register Volume 78, Number 145 (Monday, July 29, 2013)

Rules and Regulations

Pages 45447-45451

From the Federal Register Online via the Government Printing Office www.gpo.gov

FR Doc No: 2013-17813

=======================================================================

-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

Federal Energy Regulatory Commission

18 CFR Part 40

Docket No. RM12-19-000; Order No. 782

Revisions to Modeling, Data, and Analysis Reliability Standard

AGENCY: Federal Energy Regulatory Commission.

ACTION: Final rule.

-----------------------------------------------------------------------

SUMMARY: In this Final Rule, pursuant to section 215 of the Federal Power Act, the Federal Energy Regulatory Commission (Commission) approves Modeling, Data, and Analysis (MOD) Reliability Standard MOD-

028-2, submitted to the Commission for approval by the North American Electric Reliability Corporation (NERC), the Commission-certified Electric Reliability Organization. The Commission finds that the proposed Reliability Standard represents an improvement over the currently-effective standard, MOD-028-1 because the proposed Reliability Standard clarifies the timing and frequency of Total Transfer Capability calculations needed for Available Transfer Capability calculations. The Commission also approves NERC's proposed implementation plan and retirement of the currently-effective standard.

DATES: This rule is effective September 27, 2013.

FOR FURTHER INFORMATION CONTACT:

Rachel Bryant (Legal Information), Office of General Counsel, Federal Energy Regulatory Commission, 888 First Street, NE., Washington, DC 20426, (202) 502-6155, rachel.bryant@ferc.gov.

Syed Ahmad (Technical Information), Office of Electric Reliability, Federal Energy Regulatory Commission, 888 First Street, NE., Washington, DC 20426, (202) 502-8718, syed.ahmad@ferc.gov.

Christopher Young (Technical Information), Office of Energy of Energy Policy and Innovation, Federal Energy Regulatory Commission, 888 First Street, NE., Washington, DC 20426, (202) 502-6403, christopher.young@ferc.gov.

SUPPLEMENTARY INFORMATION:

144 FERC 61,027

United States Of America

Federal Energy Regulatory Commission

Before Commissioners: Jon Wellinghoff, Chairman; Philip D. Moeller, John R. Norris, Cheryl A. LaFleur, and Tony Clark.

Page 45448

Final Rule

Issued July 18, 2013.

  1. Pursuant to section 215 of the Federal Power Act (FPA),\1\ the Commission approves Modeling, Data, and Analysis (MOD) Reliability Standard MOD-028-2 submitted to the Commission by the North American Electric Reliability Corporation (NERC), the Commission-certified Electric Reliability Organization (ERO). NERC submitted one modification to the currently-effective Reliability Standard MOD-028-1, pertaining to the information a transmission service provider \2\ must include when calculating Total Transfer Capability (TTC) using the area interchange methodology for the on-peak and off-peak intra-day and next day time periods. The Commission also approves NERC's proposed implementation plan and retirement of the currently-effective Reliability Standard MOD-028-1.

    ---------------------------------------------------------------------------

    \1\ 16 U.S.C. 824o (2006).

    \2\ NERC defines ``transmission service provider'' as ``the entity that administers the transmission tariff and provides Transmission Service to Transmission Customers under applicable transmission service agreements.'' NERC, Glossary of Terms Used in NERC Reliability Standards 64 (2011), http://www.nerc.com/files/Glossary_of_Terms.pdf. We also use the term ``transmission operator'' in this final rule, which is defined by NERC as ``the entity responsible for the reliability of its ``local'' transmission system, and that operates or directs the operations of the transmission facilities.'' Id. These terms indicate distinct NERC functional entities, to which different requirements within the same Reliability Standard may apply. Accordingly, in the context of describing the requirement of a Reliability Standard, we necessarily use either or both terms where appropriate.

    ---------------------------------------------------------------------------

    1. Background

    1. Mandatory Reliability Standards

  2. Section 215 of the FPA requires a Commission-certified ERO to develop mandatory and enforceable Reliability Standards, subject to Commission review and approval. Specifically, the Commission may approve, by rule or order, a proposed Reliability Standard or modification to a Reliability Standard if it determines that the Standard is just, reasonable, not unduly discriminatory or preferential, and in the public interest.\3\ Once approved, the Reliability Standards may be enforced by the ERO, subject to Commission oversight, or by the Commission independently.\4\ Pursuant to section 215 of the FPA, the Commission established a process to select and certify an ERO,\5\ and subsequently certified NERC.\6\

    ---------------------------------------------------------------------------

    \3\ Id. 824o(d)(2).

    \4\ Id. 824o(e)(3).

    \5\ Rules Concerning Certification of the Electric Reliability Organization; and Procedures for the Establishment, Approval, and Enforcement of Electric Reliability Standards, Order No. 672, FERC Stats. & Regs. 31,204, order on reh'g, Order No. 672-A, FERC Stats. & Regs. 31,212 (2006).

    \6\ North American Electric Reliability Corp., 116 FERC 61,062, order on reh'g & compliance, 117 FERC 61,126 (2006), aff'd sub nom. Alcoa, Inc. v. FERC, 564 F.3d 1342 (D.C. Cir. 2009).

    ---------------------------------------------------------------------------

  3. In March 2007, the Commission issued Order No. 693, evaluating 107 Reliability Standards, including 23 MOD standards pertaining to methodologies for calculating Available Transfer Capability (ATC) and Available Flowgate Capability (AFC).\7\ The Commission approved one out of the 23 MOD standards unconditionally, approved nine with direction for modification and left the remaining 13 pending with direction for modification.\8\

    ---------------------------------------------------------------------------

    \7\ Mandatory Reliability Standards for the Bulk-Power System, Order No. 693, FERC Stats. & Regs. 31,242, at P 1046, order on reh'g, Order No. 693-A, 120 FERC 61,053 (2007). See also Preventing Undue Discrimination and Preference in Transmission Service, Order No. 890, FERC Stats. & Regs. 31,241, order on reh'g, Order No. 890-A, FERC Stats. & Regs. 31,261 (2007), order on reh'g, Order No. 890-B, 123 FERC 61,299 (2008), order on reh'g, Order No. 890-C, 126 FERC 61,228 (2009) (directing public utilities to develop Reliability Standards and business practices to improve the consistency and transparency of ATC calculations).

    \8\ Order No. 693, FERC Stats. & Regs. 31,242 at P 1010.

    ---------------------------------------------------------------------------

  4. On November 24, 2009, the Commission issued Order No. 729,\9\ which approved Available Transmission System Capability Reliability Standard MOD-001-1 as part of a set of Reliability Standards that pertain to methodologies for the consistent and transparent calculation of ATC and AFC. These Reliability Standards were designed to ensure, among other things, that transmission service providers maintain awareness of available system capability and future flows on their own systems, as well as those of their neighbors, and to reduce transmission service provider discretion and enhance transparency in the calculation of ATC.\10\ Requirement R1 of MOD-001-1 required a transmission operator to select one of three methodologies for calculation of ATC or AFC for each available ATC path for each time frame (hourly, daily or monthly). NERC developed these three methodologies as detailed in Reliability Standards MOD-028-1 (the area interchange methodology), MOD-029-1a (the rated system path methodology), and MOD-030-2 (the flowgate methodology).\11\

    ---------------------------------------------------------------------------

    \9\ Mandatory Reliability Standards for the Calculation of Available Transfer Capability, Capacity Benefit Margins, Transmission Reliability Margins, Total Transfer Capability, and Existing Transmission Commitments and Mandatory Reliability Standards for the Bulk Power System, Order No. 729, 129 FERC 61,155 (2009), order on clarification, Order No. 729-A, 131 FERC 61,109, order on reh'g and reconsideration, Order No. 729-B, 132 FERC 61,027 (2010).

    \10\ Order No. 729, 129 FERC 61,155 at PP 87-89.

    \11\ Id. P 51.

    ---------------------------------------------------------------------------

  5. The MOD Reliability Standards require certain users, owners, and operators of the bulk power system to develop consistent and transparent methodologies for the calculation of ATC or AFC.\12\ Three currently-effective Reliability Standards--MOD-028-1, MOD-029-1a, and MOD-030-2--address three different methodologies for calculating ATC or AFC.\13\ MOD-028-1, which describes the area interchange methodology for determining ATC, only applies to those transmission operators and transmission service providers that elect to implement this particular methodology as part of their reliability compliance with Reliability Standard MOD-001-1. MOD-001-1 requires transmission service providers to ``adhere to a specific documented and transparent methodology'' and ``to select one of three methodologies for calculating ATC or AFC for each available transfer capability path for each time frame (hourly, daily or monthly) for the facilities in its area.\14\

    ---------------------------------------------------------------------------

    \12\ Id. P 1.

    \13\ Id. P 51.

    \14\ Id. P 19.

    ---------------------------------------------------------------------------

  6. Requirement R3.1 of MOD-028-1 details the information a transmission operator must include in its TTC determination under the area interchange methodology for the on-peak and off-peak intra-day and next day time periods, as well as future days two through 31 and for months two through 13.\15\

    ---------------------------------------------------------------------------

    \15\ Id. P 57 (stating that this information includes: expected generation and transmission outages, additions, and retirements; load forecasts; and unit commitment and dispatch order).

    ---------------------------------------------------------------------------

    1. NERC Petition

  7. On August 24, 2012, NERC submitted a Petition for Approval of Proposed Reliability Standard (Petition), seeking Commission approval of a proposed Reliability Standard, MOD-028-2, Area Interchange Methodology, Requirement R3.1, which would revise the currently effective ``Version 1'' standard--MOD-028-1.

  8. NERC stated that Florida Power & Light Company (FPL) requested that NERC interpret MOD-028-1, Requirement R3.1. Specifically, FPL requested that NERC clarify whether Requirement R3.1, which instructs transmission operators to include data

    Page 45449

    ``for on peak and off peak intra-day and next day TTCs,'' actually requires transmission operators to provide separate TTC numbers for different portions of the current day. NERC explained that, upon reviewing FPL's request for interpretation, the NERC Standards Committee determined that providing this clarification might require a modification to the Standard.\16\ In its Petition, NERC asserted that it intended the language of MOD-028-1 to specify that, for TTC used in current-day and next-day ATC calculations, the load forecast used should be consistent with the period being calculated. Specifically, NERC stated:

    \16\ Petition, Exhibit E (Record of Development of Proposed Reliability Standard).

    ---------------------------------------------------------------------------

    Requirement R3 of the MOD-028-1 standard is proposed to be modified to clarify language regarding load forecasting, to indicate that for days two through 31, a daily load forecast is required (identical to the current standard); for months two through 13, a monthly load forecast is required (identical to the current standard); and for current-day and next-day, entities may use either a daily or hourly load forecast (the language being clarified). The new language clarifies and is consistent with the intent of the original requirement language, and does not materially change the standard.\17\

    \17\ Petition at 7 (emphasis added).

    ---------------------------------------------------------------------------

  9. NERC thus proposed Reliability Standard MOD-028-2, which revises MOD-028-1 as follows:

    GRAPHIC TIFF OMITTED TR29JY13.010

    1. Notice of Proposed Rulemaking

  10. On March 21, 2013, the Commission issued a Notice of Proposed Rulemaking (NOPR) proposing to approve Reliability Standard MOD-028-2 as just, reasonable, not unduly discriminatory or preferential, and in the public interest.\18\ The Commission proposed to approve Reliability Standard MOD-028-2 after determining that it clarified requirement R3.1 of Reliability Standard MOD-028-1 and did not present reliability concerns.

    ---------------------------------------------------------------------------

    \18\ Revisions to Modeling, Data, and Analysis Reliability Standard, Notice of Proposed Rulemaking, 78 FR 19,152 (Mar. 29, 2013), 142 FERC 61,210 (2013).

    ---------------------------------------------------------------------------

  11. While proposing to approve Reliability Standard MOD-028-2, the NOPR also identified possible market implications of NERC's proposed modification to requirement R3.1. The NOPR stated that, although NERC's statutory functions are properly focused on the reliability of the Bulk-Power System, the Commission has determined that the ERO should also attempt to develop Reliability Standards that have no undue negative effect on competition.\19\

    ---------------------------------------------------------------------------

    \19\ Id. P 11 (citing Order No. 729, 129 FERC 61,155 at PP 109, 135).

    ---------------------------------------------------------------------------

  12. The NOPR stated that NERC's proposed revision to requirement R3.1.2 allows a transmission operator flexibility to choose either a daily or hourly load forecast when forecasting current-day and next-day TTC. The NOPR sought comments regarding whether a transmission operator could potentially use a load forecast assumption that is not applicable to the period being calculated. As an example, the NOPR stated that a transmission operator using daily on-peak load forecasts in determining off-peak TTC for the current day could, either purposefully or inadvertently, suppress off-peak ATC used by generators that make off-

    peak sales, or other customers who purchase hourly service.

  13. Comments in support of the NOPR were filed by NERC and Southern

    Page 45450

    Company Services, Inc., acting as agent for Alabama Power Company, Georgia Power Company, Gulf Power Company, and Mississippi Power Company (Southern Company Services).

    1. Discussion

  14. Pursuant to section 215(d)(2) of the FPA, we approve Reliability Standard MOD-028-2 as just, reasonable, not unduly discriminatory or preferential, and in the public interest. The Commission also approves NERC's proposed implementation plan, i.e., that the standard shall become effective on the first day of the first calendar quarter after Commission approval, and retirement of the currently-effective Reliability Standard MOD-028-1. NERC's clarifying revision to Requirement R3.1.2 of MOD-028-2 allows a transmission operator the flexibility to choose either a daily or hourly load forecast when forecasting current-day and next-day TTC. This revision does not present reliability concerns.

  15. In the NOPR, the Commission asked for comment on a potential market-related concern regarding whether a transmission operator using daily on-peak load forecasts in determining off-peak TTC for the current day could, either purposefully or inadvertently, suppress off-

    peak ATC used by generators that make off-peak sales, or other customers who purchase hourly service. In response to the NOPR, two entities submitted comments, both supporting Commission approval of MOD-028-2. Southern Company Services comments that the flexibility in Requirement R3.1 does not give rise to the potential for undue discrimination in ATC calculations. NERC states that the proposed modification to Reliability Standard MOD-028-2 clarifies the existing language and provides flexibility for operators to select a methodology that best fits their needs. NERC comments that it ``expects that entities will implement proposed Reliability Standard MOD-028-2 consistent with their existing legal obligations, i.e., pursuant to open access transmission tariffs, etc.'' \20\ NERC adds that, ``while it might be possible for an entity to use a load forecast assumption that is not applicable to the period being calculated, the Commission can mitigate such risks through complaints and the Commission's market oversight authority.'' \21\

    ---------------------------------------------------------------------------

    \20\ NERC Comments at 3-4.

    \21\ Id. at 3.

    ---------------------------------------------------------------------------

  16. We are satisfied that the modification to Requirement R3.1 does not give rise to any immediate market-related concerns in the instant proceeding. No entity filed comments raising the concern that a transmission operator would use a load forecast assumption that is not applicable to the period being calculated. However, we agree with NERC that, consistent with Order No. 729, the risk of a transmission service provider using parameters and assumptions to skew its ATC values can be mitigated through complaints and market oversight authority.\22\ In addition, as NERC also acknowledges, transmission operators must implement the revised Reliability Standard MOD-028-2 in a manner consistent with their existing legal obligations, including their obligations under their open access transmission tariffs.\23\

    ---------------------------------------------------------------------------

    \22\ See Order No. 729, 129 FERC 61,155 at P 135.

    \23\ To the extent a market-related issue arises as a result of future changes to Reliability Standard MOD-028, we can address it at that time.

    ---------------------------------------------------------------------------

  17. Accordingly, pursuant to FPA section 215(d)(2), we approve Reliability Standard MOD-028-2.

    1. Information Collection Statement

  18. The Office of Management and Budget (OMB) regulations require that OMB approve certain reporting and recordkeeping (collections of information) imposed by an agency.\24\ The information contained here is also subject to review under section 3507(d) of the Paperwork Reduction Act of 1995.\25\

    ---------------------------------------------------------------------------

    \24\ 5 CFR 1320.11 (2012).

    \25\ 44 U.S.C. 3507(d).

    ---------------------------------------------------------------------------

  19. As stated above, the Commission previously approved, in Order No. 729, the Reliability Standard that is the subject of the current rulemaking. This Final Rule approves one revision to a previously approved Reliability Standard developed by NERC as the ERO. The minor revision relates to an existing Reliability Standard and does not add to or otherwise increase entities' current reporting burden. Thus, the revision does not materially affect the burden estimates relating to the currently effective version of the Reliability Standards presented in Order No. 729. The MOD-028-1 Reliability Standard that is subject of the approved revision was approved in Order No. 729, and the related information collection requirements were reviewed and approved, accordingly.\26\ The Commission submitted the revised Reliability Standard to OMB as a request for ``no material'' or ``nonsubstantive'' change \27\ at the NOPR stage. OMB approved the nonsubstantive change, requiring no further Commission action related to the information collection requirements.

    ---------------------------------------------------------------------------

    \26\ See Order No. 729, 129 FERC 61,155 at PP 307-312.

    \27\ This type of submittal means that there is no change to the existing burden estimates and the existing expiration date.

    ---------------------------------------------------------------------------

    1. Environmental Analysis

  20. The Commission is required to prepare an Environmental Assessment or an Environmental Impact Statement for any action that may have a significant adverse effect on the human environment.\28\ The Commission has categorically excluded certain actions from this requirement as not having a significant effect on the human environment. Included in the exclusion are rules that are clarifying, corrective, or procedural or that do not substantially change the effect of the regulations being amended.\29\ The actions proposed herein fall within this categorical exclusion in the Commission's regulations.

    ---------------------------------------------------------------------------

    \28\ Regulations Implementing the National Environmental Policy Act, Order No. 486, 52 FR 47897 (Dec. 17, 1987), FERC Stats. & Regs. Regulations Preambles 1986-1990 30,783 (1987).

    \29\ 18 CFR 380.4(a)(2)(ii).

    ---------------------------------------------------------------------------

    1. Regulatory Flexibility Act

  21. The Regulatory Flexibility Act of 1980 (RFA) \30\ generally requires a description and analysis of final rules that will have significant economic impact on a substantial number of small entities. The RFA mandates consideration of regulatory alternatives that accomplish the stated objectives of a final rule and that minimize any significant economic impact on a substantial number of small entities. The Small Business Administration's Office of Size Standards develops the numerical definition of a small business.\31\ For electric utilities, a firm is small if, including its affiliates, it is primarily engaged in the transmission, generation and/or distribution of electric energy for sale and its total electric output for the preceding twelve months did not exceed four million megawatt hours. The Commission does not expect the revision adopted herein to materially affect the cost for small entities to comply with the proposed Reliability Standard. As discussed above, the clarifying revision allows transmission service providers more flexibility in calculating ATC and only de minimis costs are associated with implementation of the revision. Therefore, the Commission certifies that the Final Rule will not have a significant economic impact on a substantial number of small entities.

    ---------------------------------------------------------------------------

    \30\ 5 U.S.C. 601-612.

    \31\ See 13 CFR 121.201.

    ---------------------------------------------------------------------------

    Page 45451

    1. Document Availability

  22. In addition to publishing the full text of this document in the Federal Register, the Commission provides all interested persons an opportunity to view and/or print the contents of this document via the Internet through the Commission's Home Page (http://www.ferc.gov) and in the Commission's Public Reference Room during normal business hours (8:30 a.m. to 5:00 p.m. Eastern time) at 888 First Street NE., Room 2A, Washington, DC 20426.

  23. From the Commission's Home Page on the Internet, this information is available on eLibrary. The full text of this document is available on eLibrary in PDF and Microsoft Word format for viewing, printing, and/or downloading. To access this document in eLibrary, type the docket number excluding the last three digits of this document in the docket number field.

  24. User assistance is available for eLibrary and the Commission's Web site during normal business hours from the Commission's Online Support at (202) 502-6652 (toll free at 1-866-208-3676) or email at ferconlinesupport@ferc.gov, or the Public Reference Room at (202) 502-

    8371, TTY (202)502-8659. Email the Public Reference Room at public.referenceroom@ferc.gov.

    1. Effective Date and Congressional Notification

  25. These regulations are effective September 27, 2013. The Commission has determined, with the concurrence of the Administrator of the Office of Information and Regulatory Affairs of OMB, that this rule is not a ``major rule'' as defined in section 351 of the Small Business Regulatory Enforcement Fairness Act of 1996.

    By the Commission.

    Kimberly D. Bose,

    Secretary.

    FR Doc. 2013-17813 Filed 7-26-13; 8:45 am

    BILLING CODE 6717-01-P