Revisions to the Unregulated Contaminant Monitoring Rule (UCMR 4) for Public Water Systems and Announcement of a Public Meeting

Federal Register, Volume 80 Issue 238 (Friday, December 11, 2015)

Federal Register Volume 80, Number 238 (Friday, December 11, 2015)

Proposed Rules

Pages 76897-76923

From the Federal Register Online via the Government Publishing Office www.gpo.gov

FR Doc No: 2015-30824

-----------------------------------------------------------------------

ENVIRONMENTAL PROTECTION AGENCY

40 CFR Part 141

EPA-HQ-OW-2015-0218; FRL-9935-74-OW

RIN 2040-AF10

Revisions to the Unregulated Contaminant Monitoring Rule (UCMR 4) for Public Water Systems and Announcement of a Public Meeting

AGENCY: Environmental Protection Agency (EPA).

ACTION: Proposed rule and notice of public meeting.

-----------------------------------------------------------------------

SUMMARY: The U.S. Environmental Protection Agency (EPA) is proposing a Safe Drinking Water Act (SDWA) rule that requires public water systems to collect occurrence data for contaminants that may be present in tap water but are not yet subject to EPA's drinking water standards set under SDWA. This rule, revised every five years as required by SDWA, benefits public health by providing EPA and other interested parties with scientifically valid data on the national occurrence of selected contaminants in drinking water, such as cyanotoxins associated with harmful algal blooms. This data set is one of the primary sources of information on occurrence, levels of exposure and population exposure the Agency uses to develop regulatory decisions for emerging contaminants in the public drinking water supply. This proposal identifies eleven analytical methods to support water system monitoring for a total of 30 chemical contaminants/groups, consisting of ten cyanotoxins/groups; two metals; eight pesticides plus one pesticide manufacturing byproduct (hereinafter collectively referred to as ``pesticides''); three brominated haloacetic acid groups of disinfection byproducts; three alcohols; and three semivolatile organic chemicals. EPA is also announcing a public webinar to discuss this proposal of the fourth Unregulated Contaminant Monitoring Rule.

DATES: Comments must be received on or before February 9, 2016. Under the Paperwork Reduction Act (PRA), comments on the information collection provisions are best assured of consideration if the Office of Management and Budget (OMB) receives a copy of your comments on or before January 11, 2016. The public webinar will be held on January 13, 2016, from 1:00 p.m.. to 4:30 p.m., eastern time. Persons wishing to participate in the webinar must register

Page 76898

by January 10, 2016, as described in section II.M.

ADDRESSES: Submit your comments, identified by Docket ID No. EPA-HQ-OW-

2015-0218, at http://www.regulations.gov. Follow the online instructions for submitting comments. Once submitted, comments cannot be edited or removed from Regulations.gov. The EPA may publish any comment received to its public docket. Do not submit electronically any information you consider to be Confidential Business Information (CBI) or other information whose disclosure is restricted by statute. Multimedia submissions (audio, video, etc.) must be accompanied by a written comment. The written comment is considered the official comment and should include discussion of all points you wish to make. The EPA will generally not consider comments or comment contents located outside of the primary submission (i.e. on the web, cloud, or other file sharing system). For additional submission methods, the full EPA public comment policy, information about CBI or multimedia submissions, and general guidance on making effective comments, please visit http://www2.epa.gov/dockets/commenting-epa-dockets.

FOR FURTHER INFORMATION CONTACT: Brenda D. Parris, Standards and Risk Management Division (SRMD), Office of Ground Water and Drinking Water (OGWDW) (MS 140), Environmental Protection Agency, 26 West Martin Luther King Drive, Cincinnati, OH 45268; telephone number: (513) 569-

7961; or email address: parris.brenda@epa.gov; or Melissa Simic, SRMD, OGWDW (MS 140), Environmental Protection Agency, 26 West Martin Luther King Drive, Cincinnati, Ohio 45268; telephone number: (513) 569-7864; or email address: simic.melissa@epa.gov. For general information, contact the Safe Drinking Water Hotline. Callers within the United States can reach the Hotline at (800) 426-4791. The Hotline is open Monday through Friday, excluding federal holidays, from 10 a.m. to 4 p.m., eastern time. The Safe Drinking Water Hotline can also be found on the Internet at: http://water.epa.gov/drink/hotline/.

SUPPLEMENTARY INFORMATION:

Table of Contents

I. General Information

  1. Does this action apply to me?

  2. What action is the Agency taking and why?

  3. What is the Agency's authority for taking this action?

  4. What is the estimated cost of this proposed action?

    II. Background

  5. How has EPA implemented the Unregulated Contaminant Monitoring Program?

  6. How are the Contaminant Candidate List (CCL), the UCMR program, the Regulatory Determination process and the NCOD interrelated?

  7. What notable changes are being proposed for UCMR 4?

  8. How did EPA prioritize candidate contaminants and what contaminants are proposed for UCMR 4?

  9. What is the proposed applicability date?

  10. What are the proposed UCMR 4 sampling design and timeline of activities?

    1. Sampling Frequency, Timing

    2. Sampling Locations

    3. Phased Sample Analysis for Microcystins

    4. Representative Sampling

    5. Summary

  11. What are reporting requirements for UCMR 4?

    1. Data Elements

    2. Duplicate Samples

  12. What are Minimum Reporting Levels (MRLs) and how were they determined?

    I. How do laboratories become approved to conduct UCMR 4 analyses?

    1. Request to Participate

    2. Registration

    3. Application Package

    4. EPA's Review of Application Package

    5. Proficiency Testing

    6. Written EPA Approval

  13. What documents are being incorporated by reference?

    1. Methods From the U.S. Environmental Protection Agency

    2. Methods From ``ASTM International''

    3. Methods From ``Standard Methods for the Examination of Water & Wastewater''

    4. Methods From ``Standard Methods Online''

    5. Method From ``Ohio EPA''

  14. What is the states' role in the UCMR program?

    L. What stakeholder meetings have been held in preparation for UCMR 4?

  15. How do I participate in the upcoming stakeholder meeting?

    1. Webinar Participation

    2. Webinar Materials

  16. How did EPA consider Children's Environmental Health?

  17. How did EPA address Environmental Justice?

    III. Statutory and Executive Order Reviews

  18. Executive Order 12866: Regulatory Planning and Review and Executive Order 13563: Improving Regulation and Regulatory Review

  19. Paperwork Reduction Act (PRA)

  20. Regulatory Flexibility Act (RFA)

  21. Unfunded Mandates Reform Act (UMRA)

  22. Executive Order 13132: Federalism

  23. Executive Order 13175: Consultation and Coordination With Indian Tribal Governments

  24. Executive Order 13045: Protection of Children From Environmental Health Risks and Safety Risks

  25. Executive Order 13211: Actions Concerning Regulations That Significantly Affect Energy Supply, Distribution or Use

    I. National Technology Transfer and Advancement Act and 1 CFR Part 51

  26. Executive Order 12898: Federal Actions To Address Environmental Justice in Minority Populations and Low-Income Populations

    IV. References

    Abbreviations and Acronyms

    mug/L Microgram per liter

    ADDA (2S, 3S, 8S, 9S, 4E, 6E)-3-amino-9-methoxy-2,6,8-trimethyl-10-

    phenyl-4, 6-decadienoic acid

    ASDWA Association of State Drinking Water Administrators

    ASTM ASTM International

    CAS Chemical Abstract Service

    CBI Confidential Business Information

    CCC Continuing Calibration Check

    CCL Contaminant Candidate List

    CFR Code of Federal Regulations

    CLDA Chlorine Dioxide Applied After SR Sample Location

    CLDB Chlorine Dioxide Applied Before SR Sample Location

    CWS Community Water System

    DBPR Disinfectants and Disinfection Byproducts Rule

    DSMRT Distribution System Maximum Residence Time

    ELISA Enzyme-linked Immunosorbent Assay

    EPA United States Environmental Protection Agency

    EPTDS Entry Point to the Distribution System

    FR Federal Register

    GC Gas Chromatography

    GC/ECD Gas Chromatography/Electron Capture Detection

    GC/MS Gas Chromatography/Mass Spectrometry

    GW Ground Water

    GWUDI Ground Water Under the Direct Influence of Surface Water

    HAAs Haloacetic Acids

    HAA5 Dibromoacetic Acid, Dichloroacetic Acid, Monobromoacetic Acid, Monochloroacetic Acid, Trichloroacetic Acid

    HAA6Br Bromochloroacetic Acid, Bromodichloroacetic Acid, Dibromoacetic Acid, Dibromochloroacetic Acid, Monobromoacetic Acid, Tribromoacetic Acid

    HAA9 Bromochloroacetic Acid, Bromodichloroacetic Acid, Chlorodibromoacetic Acid, Dibromoacetic Acid, Dichloroacetic Acid, Monobromoacetic Acid, Monochloroacetic Acid, Tribromoacetic Acid, Trichloroacetic Acid

    HPXA Hydrogen Peroxide Applied After Source Water Sample Location

    HPXB Hydrogen Peroxide Applied Before Source Water Sample Location

    IC-MS/MS Ion Chromatography/Tandem Mass Spectrometry

    ICP-MS Inductively Coupled Plasma Mass Spectrometry

    ICR Information Collection Request

    IDC Initial Demonstration of Capability

    IS Internal Standard

    LFB Laboratory Fortified Blank

    Page 76899

    LRB Laboratory Reagent Blank

    LCMRL Lowest Concentration Minimum Reporting Level

    LC/ECI-MS/MS Liquid Chromatography/Electrospray Ionization/Tandem Mass Spectrometry

    LC/MS/MS Liquid Chromatography/Tandem Mass Spectrometry

    LT2 Long Term 2 Enhanced Surface Water Treatment Rule

    M Million

    MRL Minimum Reporting Level

    NAICS North American Industry Classification System

    NCOD National Drinking Water Contaminant Occurrence Database

    NPDWRs National Primary Drinking Water Regulations

    NTNCWS Non-transient Non-community Water System

    OGWDW Office of Ground Water and Drinking Water

    OMB Office of Management and Budget

    PA Partnership Agreement

    PEMA Permanganate Applied After Source Water Sample Location

    PEMB Permanganate Applied Before Source Water Sample Location

    PRA Paperwork Reduction Act

    PT Proficiency Testing

    PWS Public Water System

    QCS Quality Control Sample

    QH Quality HAA Sample

    RFA Regulatory Flexibility Act

    SDWA Safe Drinking Water Act

    SDWARS Safe Drinking Water Accession and Review System

    SDWIS/Fed Federal Safe Drinking Water Information System

    SM Standard Methods

    SMP State Monitoring Plan

    SOP Standard Operating Procedure

    SPE Solid Phase Extraction

    SR Source Water

    SRF Drinking Water State Revolving Fund

    SRMD Standards and Risk Management Division

    SUR Surrogate Standard

    SVOCs Semivolatile Organic Chemicals

    SW Surface Water

    TNCWS Transient Non-Community Water System

    TOC Total Organic Carbon

    UCMR Unregulated Contaminant Monitoring Rule

    UMRA Unfunded Mandates Reform Act of 1995

    USEPA United States Environmental Protection Agency

    I. General Information

  27. Does this action apply to me?

    Public water systems (PWSs) would be regulated by this proposed, fourth Unregulated Contaminant Monitoring Rule (UCMR 4). PWSs are systems that provide water for human consumption through pipes, or other constructed conveyances, to at least 15 service connections or that regularly serve an average of at least 25 individuals daily at least 60 days out of the year. Under this proposal, all large community and non-transient non-community water systems (NTNCWSs) serving more than 10,000 people would be required to monitor. A community water system (CWS) means a PWS that has at least 15 service connections used by year-round residents or regularly serves at least 25 year-round residents. A NTNCWS means a PWS that is not a CWS and that regularly serves at least 25 of the same people over six months per year. A nationally representative sample of CWSs and NTNCWSs serving 10,000 or fewer people would also be required to monitor (see ``Statistical Design and Sample Selection for the Unregulated Contaminant Monitoring Regulation'' (USEPA, 2001b) for a description of the statistical approach for the nationally representative sample). As is generally the case for UCMR monitoring, transient non-community water systems (TNCWSs) (i.e., non-community water systems that do not regularly serve at least 25 of the same people over six months per year) would not be required to monitor under UCMR 4. States, territories and tribes, with primary enforcement responsibility (primacy) to administer the regulatory program for PWSs under SDWA, can participate in the implementation of UCMR 4 through Partnership Agreements (PAs) (see discussion of PAs in section II.K). Primacy agencies with PAs can choose to be involved in various aspects of the UCMR 4 monitoring for PWSs they oversee; however, the PWS remains responsible for compliance. Potentially regulated categories and entities are identified in the following table.

    ------------------------------------------------------------------------

    Examples of

    Category potentially regulated NAICS \a\

    entities

    ------------------------------------------------------------------------

    State, local, & tribal States, local and 924110

    governments. tribal governments

    that analyze water

    samples on behalf of

    PWSs required to

    conduct such

    analysis; states,

    local and tribal

    governments that

    directly operate

    CWSs and NTNCWSs

    required to monitor.

    Industry...................... Private operators of 221310

    CWSs and NTNCWSs

    required to monitor.

    Municipalities................ Municipal operators 924110

    of CWSs and NTNCWSs

    required to monitor.

    ------------------------------------------------------------------------

    \a\ NAICS = North American Industry Classification System.

    This table is not intended to be exhaustive, but rather provides a guide for readers regarding entities likely to be regulated by this action. This table summarizes the types of entities that EPA is aware could potentially be regulated by this action. If you are uncertain whether your entity is regulated by this action after carefully examining the definition of PWS found in Sec. Sec. 141.2 and 141.3, and the applicability criteria found in Sec. 141.40(a)(1) and (2) of Title 40 in the Code of Federal Regulations (CFR), please consult the contacts listed in the preceding FOR FURTHER INFORMATION CONTACT section.

  28. What action is the Agency taking and why?

    EPA is proposing a rule to require PWSs to analyze drinking water samples for unregulated contaminants that do not have health based standards set under SDWA and to report their results to EPA. This will be the fourth national monitoring effort under the UCMR program (see section II.D). The monitoring provides data to inform future regulatory actions to protect public health.

    The public will benefit from information about whether or not unregulated contaminants are present in their drinking water. If contaminants are not found, consumer confidence in their drinking water will improve. If contaminants are found, illnesses may be avoided when subsequent actions, such as regulations, reduce or eliminate those contaminants.

  29. What is the Agency's authority for taking this action?

    As part of its responsibilities under SDWA, EPA implements section 1445(a)(2), Monitoring Program for Unregulated Contaminants. This section, as amended in 1996, requires that once every five years, beginning in August 1999, EPA issue a list of no more than 30 unregulated contaminants to be monitored by PWSs. SDWA requires that EPA enter the monitoring data into the Agency's publically available National Contaminant Occurrence Database (NCOD). EPA's UCMR program must ensure that systems serving a population larger than 10,000 people, as well as a nationally representative

    Page 76900

    sample of PWSs serving 10,000 or fewer people, are required to monitor. EPA must vary the frequency and schedule for monitoring based on the number of persons served, the source of supply and the contaminants likely to be found. EPA is using this authority as the basis for monitoring 29 of the 30 contaminants/groups proposed under this rule.

    Section 1445(a)(1)(A) of SDWA, as amended in 1996, requires that every person who is subject to any SDWA requirement establish and maintain such records, make such reports, conduct such monitoring and provide such information as the Administrator may reasonably require by regulation to assist the Administrator in establishing SDWA regulations. Pursuant to this provision, EPA can also require the monitoring of contaminants already subject to EPA's drinking water standards. EPA is using this authority as the basis for monitoring one of the chemical groups (Haloacetic Acids 5 (HAA5)) proposed under this rule. Sample collection and analysis for HAA5 can be done concurrent with the unregulated HAA monitoring described in section II.F (resulting in no substantive additional burden) and would allow EPA to better understand co-occurrence between regulated and unregulated disinfection byproducts.

    Hereinafter, all 30 proposed contaminants/groups are collectively referred to as ``contaminants.''

  30. What is the estimated cost of this proposed action?

    EPA estimates the total average national cost of this proposed action will be $25.3 million per year from 2017-2021. EPA has documented the assumptions and data sources used in the preparation of this estimate in the Information Collection Request (ICR) (USEPA, 2015a). EPA proposes using eleven analytical methods (eight EPA-

    developed analytical methods, one state-developed methodology and two alternate equivalent consensus organization-developed methods) to analyze samples for 30 UCMR 4 chemical contaminants. EPA's estimate of the analytical cost for the UCMR 4 contaminants and related indicators is $2,562 per sample set. EPA calculated these costs by summing the laboratory unit cost of each method. Exhibit 1 presents a breakdown of EPA estimated annual average national costs. Estimated PWS (i.e., large and very large) and EPA costs reflect the analytical cost (i.e., non-

    labor) for all UCMR 4 methods. EPA pays for the analytical costs for all systems serving a population of 10,000 or fewer people. Laboratory analysis and sample shipping account for approximately 80% of the total national cost for UCMR 4 implementation. EPA estimated laboratory unit costs based on consultations with multiple commercial drinking water laboratories and, in the case of new methods, a review of the costs of analytical methods similar to those proposed in this action. The cost of the laboratory methods includes shipping as part of the cost for the analysis.

    EPA expects that states would incur labor costs associated with voluntary assistance with UCMR 4 implementation. EPA estimated state costs using the relevant assumptions from the State Resource Model that was developed by the Association of State Drinking Water Administrators (ASDWA) (ASDWA, 2013) to help states forecast resource needs. Model estimates were adjusted to account for actual levels of state participation under UCMR 3. State participation is voluntary; thus, the level of effort is expected to vary among states and would depend on their individual agreements with EPA.

    EPA assumes that one-third of the systems would monitor during each of the three monitoring years from January 2018 through December 2020. The total estimated annual costs (labor and non-labor) would be incurred as follows:

    Exhibit 1--Estimated Average Annual Costs of UCMR 4

    ------------------------------------------------------------------------

    Avg. annual cost

    Respondent all respondents

    (2017-2021) \ 1\

    ------------------------------------------------------------------------

    Small Systems (25-10,000), including labor \2\ only $0.16 m

    (non-labor costs \3\ paid for by EPA)...............

    Large Systems (10,001-100,000), including labor and $15.7 m

    non-labor costs.....................................

    Very Large Systems (100,001 and greater), including $4.3 m

    labor and non-labor costs...........................

    States, including labor costs related to $0.50 m

    implementation coordination.........................

    EPA, including labor for implementation, non-labor $4.7 m

    for small system testing............................

    ------------------------------------------------------------------------

    AVERAGE ANNUAL NATIONAL TOTAL.................... $25.3 m

    ------------------------------------------------------------------------

    \1\ Totals may not equal the sum of components due to rounding.

    \2\ Labor costs pertain to systems, states and EPA. Costs include

    activities such as reading the rule, notifying systems selected to

    participate, sample collection, data review, reporting and record

    keeping.

    \3\ Non-labor costs would be incurred primarily by EPA and by very large

    and large PWSs. They include the cost of shipping samples to

    laboratories for testing and the cost of the laboratory analyses.

    Additional details regarding EPA's cost assumptions and estimates can be found in the ``DRAFT Information Collection Request for the Unregulated Contaminant Monitoring Rule (UCMR 4)'' (USEPA, 2015a) ICR Number 2192.07, which presents estimated cost and burden for the 2017-

    2019 period, consistent with the 3-year time frame for ICRs. Estimates of costs over the entire 5-year UCMR 4 sequence of 2017-2021 are attached as an appendix to the ICR. Copies of the ICR and its appendix may be obtained from the EPA public docket for this proposed rule, under Docket ID No. EPA-HQ-OW-2015-0218.

    II. Background

  31. How has EPA implemented the unregulated contaminant monitoring program?

    EPA published the list of contaminants for the first UCMR (UCMR 1) in the Federal Register (FR) on September 17, 1999 (64 FR 50556, (USEPA, 1999)), the second UCMR (UCMR 2) on January 4, 2007 (72 FR 368, (USEPA, 2007)) and the third UCMR (UCMR 3) on May 2, 2012 (77 FR 26072, (USEPA, 2012c)). EPA established a three-tiered approach for monitoring contaminants under the UCMR program that takes into account the availability of analytical methods, the source of water supply and the contaminants likely to be found. Assessment Monitoring for ``List 1'' contaminants typically relies on analytical methods, techniques or technologies that are in common use by drinking water laboratories. Screening Survey monitoring for ``List 2''

    Page 76901

    contaminants typically relies on newer analytical methods that are not as commonly used, such that laboratory capacity to perform List 2 analyses may be limited. Finally, Pre-Screen Testing for ``List 3'' contaminants is often associated with analytical methods that are very recently developed and/or are particularly complex. In addition to method complexity and laboratory capacity, EPA considers sampling frequency and/or the relevant universe of PWSs when deciding which of the three tiers is appropriate for a contaminant.

    EPA designed the Assessment Monitoring sampling approach (USEPA, 2001b) to ensure that sample results would yield a high level of confidence and a low margin of error. The design for a nationally representative sample of small systems called for the sample to be stratified by water source type (ground water (GW) or surface water (SW)), service size category and state (where each state is allocated a minimum of two systems in its state monitoring plan (SMP)).

    This action proposes 30 contaminants for List 1, Assessment Monitoring from 2018-2020, with pre-monitoring activity in 2017 and post-monitoring activity in 2021. EPA developed this proposal after considering input from an EPA-state workgroup as well as other stakeholders.

  32. How are the Contaminant Candidate List (CCL), the UCMR program, the Regulatory Determination process and the NCOD interrelated?

    Under the 1996 amendments to SDWA, Congress established a stepwise, risk-based approach for determining which contaminants would become subject to drinking water standards. Under the first step, EPA is required to publish, every five years, a list of contaminants that are not yet regulated but which are known or anticipated to occur in PWSs; this is the Contaminant Candidate List (CCL). Under the second step, EPA must require, every five years, monitoring of up to 30 unregulated contaminants to determine their occurrence in drinking water systems; this is the UCMR program. Under the third step, EPA is required to determine, every five years, whether or not at least five contaminants from the CCL warrant regulation, based in part on the UCMR occurrence information; this is known as a Regulatory Determination where the following questions are evaluated:

    (1) Which contaminants may have an adverse effect on human health?

    (2) Which contaminants are known to occur or are likely to occur in drinking water with a frequency and at levels of public health concern?

    (3) Does regulation of such contaminants present a meaningful opportunity for risk reduction? Finally, SDWA requires EPA to issue national primary drinking water regulations (NPDWRs) for contaminants the Agency determines should be regulated.

    The CCL process identifies contaminants that may require regulation, while the UCMR program helps provide the data necessary for the Regulatory Determination process outlined above. The data collected through the UCMR program are stored in the NCOD to facilitate analysis and review of contaminant occurrence, and support the Administrator's determination on whether regulation of a contaminant is in the public health interest, as required under SDWA section 1412(b)(1). UCMR results can be viewed by the public at: http://www2.epa.gov/dwucmr.

  33. What notable changes are being proposed for UCMR 4?

    This proposed action refines the existing UCMR, as reflected in the Code of Federal Regulations, to address the contaminants proposed for UCMR 4 monitoring and to reflect lessons learned through prior experience implementing UCMRs. EPA's proposed approach and rationale for changes are described in the following sections. Key aspects of the UCMR program that would remain the same, and are outside the scope of today's proposal, include direct implementation of the rule by EPA; the number and types of systems included in Assessment Monitoring for the majority of the proposed contaminants; and EPA funding for the small system testing. Proposed changes include the list of UCMR 4 contaminants, the analytical methods, monitoring time frame, sampling locations, the revised data elements outlined in Exhibit 2 and conforming and editorial changes, such as those necessary to remove requirements solely related to UCMR 3. A track-changes version of the rule language comparing UCMR 3 to the proposed changes for UCMR 4 is included in the public docket (Docket ID No. EPA-HQ-OW 2015-0218) for this proposed rule (USEPA, 2015h).

    Exhibit 2--Notable Changes Proposed for UCMR 4

    ----------------------------------------------------------------------------------------------------------------

    CFR Rule section

    ---------------------------------------------------------------- Description of rule change Corresponding

    Number Title/Description preamble section

    ----------------------------------------------------------------------------------------------------------------

    Sec. 141.40(a)(3).................. Analytes to be monitored Revises Table 1 to include a II.D

    and related new list of contaminants

    specifications. and associated analytical

    methods.

    Sec. Sec. 141.35(a) and 141.40(a). Applicability........... Revises the Federal Safe II.E

    Drinking Water Information II.F

    System (SDWIS/Fed)

    applicability date (i.e.,

    the date used to determine

    which systems are subject

    to monitoring) to December

    31, 2015.

    Revises the monitoring dates

    to January 2018 through

    December 2020.

    Page 76902

    Sec. 141.40(a)(4).................. Sampling design Updates Table 2 to change II.F

    requirements--Frequency. the sample collection time

    frame to March--November,

    and excludes December--

    February. Additionally,

    updates the frequency such

    that, with the exception of

    cyanotoxins, monitoring

    would occur every two

    months (bi-monthly) for SW

    or ground water under the

    direct influence of surface

    water (GWUDI) systems and

    every six months for GW

    systems.

    Updates Table 2 to include

    monitoring requirements for

    cyanotoxins for PWSs with

    SW and GWUDI sources at a

    frequency of twice a month

    for four consecutive months

    (for a total of eight

    cyanotoxin sampling events).

    Sec. 141.40(a)(4).................. Sampling design Specifies revised sampling II.F

    requirements--Location. locations for Assessment

    Monitoring, including HAA5

    Stage 2 compliance and/or

    distribution system maximum

    residence time (DSMRT)

    locations for the

    brominated haloacetic acids

    (HAAs), and source water

    intake locations for total

    organic carbon (TOC), total

    microcystins (i.e. the sum

    of congeners as measured by

    ADDA-ELISA), pH and

    temperature.

    Sec. 141.35(e)..................... Reporting requirements-- Updates, revises, adds and II.G.1

    Data elements. removes data elements to

    account for the

    contaminants being

    proposed, and requires the

    reporting of quality

    control data by all

    laboratories.

    Sec. 141.40(a)(4)(ii)(F)........... Small systems sampling Removes the requirement for II.G.2

    requirements--Duplicate small system duplicate

    samples. quality control samples,

    although EPA may in the

    future select a subset of

    systems to collect

    duplicate samples if the

    Agency becomes aware of a

    need to include this type

    of quality control.

    ----------------------------------------------------------------------------------------------------------------

  34. How did EPA prioritize candidate contaminants and what contaminants are proposed for UCMR 4?

    In establishing the proposed list of contaminants for UCMR 4, EPA started with a priority set of contaminants from the draft fourth Contaminant Candidate List (CCL 4), which includes 100 chemicals or chemical groups and 12 microbes (80 FR 6076, February 4, 2015 (USEPA, 2015b)). The evaluation and selection process that led to the draft CCL 4 carried forward the final list of CCL 3 contaminants (except for those with regulatory determinations), requested and evaluated contaminant nominations from the public and evaluated any new data from previous negative regulatory determinations for potential inclusion on CCL 4 (77 FR 27057, May 8, 2012 (USEPA, 2012b)).

    EPA selected the proposed UCMR 4 contaminants using a stepwise prioritization process. The first step included identifying contaminants that: (1) Were not monitored under UCMR 2 or UCMR 3; (2) are anticipated to have significant occurrence nationally; and (3) are expected to have a completed, validated drinking water method in time for rule proposal. This resulted in a set of 45 draft CCL 4 contaminants and another set of related non-CCL analytes with potential health effects of concern that can be measured concurrently using the analytical methods for the CCL contaminants. Including related non-CCL analytes creates a more cost-effective design and reduces the likelihood of needing to include them in a subsequent UCMR.

    The next step was to select contaminants associated with one or more of the following considerations: an available health assessment to facilitate regulatory determinations; high public concern; critical health endpoints (e.g., likely or suggestive carcinogen); active use (e.g., pesticides); and an occurrence data gap. This step identified 31 CCL contaminants, and 18 related non-CCL analytes that can be measured using the analytical methods for the CCL contaminants.

    During the final step, EPA considered workgroup and stakeholder input; looked at cost-effectiveness of the method/contaminant groups; considered implementation factors (e.g., laboratory capacity); and further evaluated health, occurrence, and persistence/mobility data to identify a proposed list of 30 UCMR 4 contaminants.

    Further information on this prioritization process, as well as contaminant-specific information (source, use, production, release, persistence, mobility, health effects and occurrence), that EPA used to select the proposed analyte list, is contained in ``UCMR 4 Candidate Contaminants--Information Compendium'' (USEPA, 2015i). Copies of the Compendium may be obtained from the EPA public docket for this proposed rule, under Docket ID No. EPA-HQ-OW-2015-0218.

    EPA invites comment on the proposed UCMR 4 contaminants and their associated analytical methods identified in Exhibit 3, as well as any other priority contaminants commenters wish to recommend. In particular, the Agency welcomes comments on the following contaminants that were considered by the workgroup, but not included in the proposed list because they were deemed a lower UCMR 4 priority than the contaminants identified in Exhibit 3: Legionella pneumophila and Mycobacterium avium (both are part of the draft CCL 4); ammonia (considered as an indicator of distribution system nitrification potential); and the pesticides vinclozolin, hexazinone and disulfoton (additional analytes in EPA Method 525.3). More specific information on why these contaminants were not included on the proposed list can be found in the Information Compendium (USEPA, 2015i) cited

    Page 76903

    above. In your comments, please identify the following: Any new contaminant(s) that you think the Agency should include in UCMR 4 monitoring; any contaminant(s) in Exhibit 3 that you think represent a lower priority than your new recommendation(s) or that should otherwise be removed from the list; the recommended analytical method(s) for any new contaminant(s) that you propose; and other relevant details (e.g., reporting level, sampling location and sampling frequency). Comments that provide supporting data or rationale are especially helpful to the Agency.

    Exhibit 3--30 Proposed UCMR 4 Analytes

    ------------------------------------------------------------------------

    ------------------------------------------------------------------------

    List 1 Analytes

    ------------------------------------------------------------------------

    One Cyanotoxin Group Using ELISA \1\

    ------------------------------------------------------------------------

    total microcystins

    ------------------------------------------------------------------------

    Seven Cyanotoxins Using EPA Method 544 (SPE LC/MS/MS) \2\

    ------------------------------------------------------------------------

    microcystin-LA microcystin-RR

    microcystin-LF microcystin-YR

    microcystin-LR Nodularin

    microcystin-LY

    ------------------------------------------------------------------------

    Two Cyanotoxins Using EPA Method 545 (LC/ECI-MS/MS) \3\

    ------------------------------------------------------------------------

    anatoxin-a Cylindrospermopsin

    ------------------------------------------------------------------------

    Two Metals Using EPA Method 200.8 (ICP-MS) \4\ or Alternate SM \5\ or

    ASTM \6\

    ------------------------------------------------------------------------

    Germanium Manganese

    ------------------------------------------------------------------------

    Nine Pesticides Using EPA Method 525.3 (SPE GC/MS) \7\

    ------------------------------------------------------------------------

    alpha-hexachlorocyclohexane Profenofos

    chlorpyrifos Tebuconazole

    Dimethipin total permethrin (cis- &

    trans-)

    Ethoprop Tribufos

    Oxyfluorfen

    ------------------------------------------------------------------------

    Three Brominated HAA Groups Using EPA Method 552.3 (GC/ECD) or 557 (IC/

    ECI-MS/MS) \8\ \9\ \10\

    ------------------------------------------------------------------------

    HAA5 HAA9

    HAA6Br

    ------------------------------------------------------------------------

    Three Alcohols Using EPA Method 541 (GC/MS) \11\

    ------------------------------------------------------------------------

    1-butanol 2-propen-1-ol

    2-methoxyethanol

    ------------------------------------------------------------------------

    Three Semivolatile Organic Chemicals (SVOCs) Using EPA Method 530 (GC/

    MS) \12\

    ------------------------------------------------------------------------

    butylated hydroxyanisole quinolone

    o-toluidine

    ------------------------------------------------------------------------

    \1\ ELISA Standard Operating Procedure (SOP) (Ohio EPA, 2015). EPA

    anticipates having an EPA ELISA method available by the publication of

    the final rule and anticipates that this method will be similar to the

    Ohio EPA methodology. Monitoring includes measuring for pH using one

    of the following methods: EPA Method 150.1 and 150.2 (USEPA, 1983a and

    1983b), ASTM D1293-12 (ASTM, 2012a), SM 4500-H+ B (SM, 2005c), SM 4500-

    H+ B-00 (SM Online, 2000a). Monitoring also includes measuring for

    water temperature using one of the following methods: SM 2550 (SM,

    2005a) or SM 2550-10 (SM Online, 2010).

    \2\ EPA Method 544 (Solid Phase Extraction (SPE) Liquid chromatography/

    tandem mass spectrometry (LC/MS/MS)) (USEPA, 2015f). This method would

    only be used if analyses by ELISA (for ``total microcystins'') yielded

    results above reporting limits.

    \3\ EPA Method 545 (Liquid chromatography/electrospray ionization/tandem

    mass spectrometry (LC/ESI-MS/MS)) (USEPA, 2015g).

    \4\ EPA Method 200.8 (Inductively coupled plasma mass spectrometry (ICP-

    MS)) (USEPA, 1994).

    \5\ Standard Methods (SM) 3125 (SM, 2005b) or SM 3125-09 (SM Online,

    2009).

    \6\ ASTM International (ASTM) D5673-10 (ASTM, 2010).

    \7\ EPA Method 525.3 (SPE Gas chromatography/mass spectrometry (GC/MS))

    (USEPA, 2012a).

    \8\ EPA Method 552.3 (GC/Electron capture detection (ECD)) (USEPA, 2003)

    and EPA Method 557 (Ion chromatography-electrospray ionization-tandem

    mass spectrometry (IC-ESI-MS/MS)) (USEPA, 2009b). HAA5 includes:

    dibromoacetic acid, dichloroacetic acid, monobromoacetic acid,

    monochloroacetic acid, trichloroacetic acid. HAA6Br includes:

    bromochloroacetic acid, bromodichloroacetic acid, dibromoacetic acid,

    dibromochloroacetic acid, monobromoacetic acid, tribromoacetic acid.

    HAA9 includes: bromochloroacetic acid, bromodichloroacetic acid,

    chlorodibromoacetic acid, dibromoacetic acid, dichloroacetic acid,

    monobromoacetic acid, monochloroacetic acid, tribromoacetic acid,

    trichloroacetic acid.

    \9\ Regulated HAAs (HAA5) are included in the proposed monitoring

    program to gain a better understanding of co-occurrence with currently

    unregulated disinfection byproducts.

    \10\ Brominated HAA monitoring also includes sampling for indicators TOC

    and bromide using methods approved for compliance monitoring. TOC

    methods include: SM 5310B, SM 5310C, SM 5310D (SM, 2005d, 2005e,

    2005f), or SM 5310B-00, SM 5310C-00, SM 5310D-00 (SM Online, 2000b,

    2000c, 2000d), EPA Method 415.3 (Rev. 1.1 or 1.2) (USEPA, 2005,

    2009a). Bromide methods include: EPA Methods 300.0 (Rev. 2.1), 300.1

    (Rev. 1.0), 317.0 (Rev. 2.0), 326.0 (Rev. 1.0) (USEPA, 1993, 1997,

    2001a, 2002) or ASTM D 6581-12 (ASTM, 2012b).

    \11\ EPA Method 541 (GC/MS) (USEPA, 2015e).

    \12\ EPA Method 530 (GC/MS) (USEPA, 2015d).

    Page 76904

  35. What is the proposed applicability date?

    EPA proposes (in Sec. 141.40(a)) a new applicability date of December 31, 2015. That is, the determination of whether a PWS is required to monitor under UCMR 4 is based on the type of system (e.g., CWS, NTNCWS, etc.) and its retail population served, as indicated by the SDWIS/Fed inventory on December 31, 2015. If a PWS believes its retail population served in SDWIS/Fed is inaccurate, the system should contact its state to verify its population as of the applicability date and request a correction if necessary. The 5-year UCMR 4 program would take place from January 2017 through December 2021.

  36. What are the proposed UCMR 4 sampling design and timeline of activities?

    The proposed rule identifies sampling and analysis for List 1 contaminants within the 2018 to 2020 time frame. Preparations prior to 2018 are expected to include coordination of laboratory approval, selection of representative small systems, development of SMPs and establishment of monitoring schedules. EPA anticipates that there is enough laboratory capacity to meet the needs of Assessment Monitoring. Exhibit 4 illustrates the major activities that we expect will take place in preparation for and during the implementation of UCMR 4.

    Exhibit 4--Proposed Timeline of UCMR 4 Activities

    ----------------------------------------------------------------------------------------------------------------

    2017 2018 2019 2020 2021

    ----------------------------------------------------------------------------------------------------------------

    After proposed rule publication: larr Assessment Monitoring rarr Complete reporting

    EPA and analysis of

    laboratory approval program List 1 Contaminants data.

    begins.

    After final rule publication: EPA/ All large systems serving more than 10,000 people;

    state

    primacy authorities (1) develop 800 small systems serving 10,000 or fewer people

    SMPs

    (including the nationally for cyanotoxins;

    representa-

    tive sample); and (2) inform 800 small systems serving 10,000 or fewer people

    PWSs/

    establish monitoring plans. for the 20 additional chemicals.

    ----------------------------------------------------------------------------------------------------------------

    To minimize the impact of the rule on small systems (those serving 10,000 or fewer people), EPA pays for the sample kit preparation, sample shipping fees and analysis costs for these systems. In addition, no small system would be required to monitor for both cyanotoxins and the 20 additional UCMR chemicals. Consistent with prior UCMRs, large systems (those serving more than 10,000 people) pay for all costs associated with their monitoring. A summary of the estimated number of systems subject to monitoring is shown in Exhibit 5.

    Exhibit 5--Systems To Participate in UCMR 4 Monitoring

    ----------------------------------------------------------------------------------------------------------------

    National sample assessment monitoring

    ------------------------------------------------------ Total number of

    System size (number of people served) 20 Additional List 1 systems per size

    10 List 1 cyanotoxins chemicals category

    ----------------------------------------------------------------------------------------------------------------

    Small Systems: \1\

    25-10,000.......................... 800 randomly selected SW 800 randomly selected SW, 1,600

    or GWUDI systems. GWUDI and GW systems.

    Large Systems: \2\

    10,001 and over.................... All SW or GWUDI systems All SW, GWUDI and GW 4,292

    (1,987). systems (4,292).

    ------------------------------------------------------------------------

    Total.......................... 2,787.................... 5,092.................... 5,892

    ----------------------------------------------------------------------------------------------------------------

    \1\ Total for small systems is additive because these systems would only be selected for one component of UCMR 4

    sampling (10 cyanotoxins or 20 additional chemicals). EPA would pay for all analytical costs associated with

    monitoring at small systems.

    \2\ Large system counts are approximate. The number of large systems is not additive. All SW and GWUDI systems

    would monitor for cyanotoxins; those same systems would also monitor for the 20 additional List 1 chemicals,

    as would the large GW systems.

    1. Sampling Frequency, Timing

      The number of samples for SW, GWUDI and GW systems would generally be consistent with those during prior UCMR cycles, with the exceptions noted for the monitoring of cyanotoxins. Water systems would be required to collect samples during the monitoring time frame of March through November (excluding December, January and February). With the exception of cyanotoxin monitoring, sampling would take place every two months for SW and GWUDI systems (a total of four sampling events), and at 6-month intervals for GW systems (a total of two sampling events). For cyanotoxin monitoring, SW and GWUDI systems would collect samples twice a month for four consecutive months (total of eight sampling events). GW systems would be excluded from cyanotoxin monitoring.

      The Assessment Monitoring sampling time frame would take place during the compressed period of March through November to better reflect the times of year when contaminants are more likely to occur in drinking water. Populations of cyanobacteria generally peak when water temperature is highest (Graham et al., 2008). Seasonality of pesticide occurrence in surface waters has been well documented, and generally relates to the timing of pesticide applications in the watershed, rainfall or irrigation patterns and watershed size (USGS, 2014; Ryberg and Gilliom, 2015). Based on this information, EPA anticipates that sampling in the December through February time period would not accurately reflect occurrence for some of the contaminants, particularly cyanotoxins and pesticides. Industry and laboratory stakeholders have also observed that the traditional UCMR approach has the potential to underestimate exposure for some contaminants because of seasonal occurrence (Roberson and Eaton, 2014). Therefore, EPA is proposing that no sampling take place during those winter months, except for resampling purposes. EPA welcomes comments on this approach.

      Large system schedules (year and months of monitoring) would initially be determined by EPA in conjunction

      Page 76905

      with the states (as described in section II.K) and these PWSs would have an opportunity to modify this schedule for planning purposes or other reasons (e.g., to conduct monitoring during the months the system or the state believes are most vulnerable, spread costs over multiple years, a sampling location will be closed during the scheduled month of monitoring, etc.). PWSs would not be permitted to reschedule monitoring specifically to avoid sample collection during a suspected vulnerable period. EPA proposes to schedule and coordinate small system monitoring by working closely with partnering states. SMPs provide an opportunity for states to review and revise the initial sampling schedules that EPA proposes (see discussion of SMPs in section II.K).

    2. Sampling Locations

      Sample collection for the UCMR 4 contaminants would take place at the entry point to the distribution system (EPTDS), with the following exceptions/additions. Sampling for ``total microcystins'' (i.e., the sum of congeners as measured by ADDA-ELISA) would also take place at the source water intake (concurrent with the collection of cyanotoxin samples at the EPTDS) unless the PWS purchases 100 percent of their water. ``Consecutive systems'' would only sample for cyanotoxins at their EPTDS. Measurements for temperature and pH would take place at the source water intake (concurrent with total microcystin sampling). HAA sampling would take place in the distribution system. Sampling for TOC and bromide would take place at a single source water intake (concurrent with HAA sampling in the distribution system). The indicator data, along with the disinfectant type and water treatment information, would aid in the understanding of brominated HAA and cyanotoxin occurrence and treatment efficacy.

      For purposes of total microcystin sampling, temperature and pH measurement, and TOC and bromide sampling, EPA defines source water under UCMR as untreated water entering the water treatment plant (i.e., at a location prior to any treatment). Systems that are subject to the Long Term 2 Enhanced Surface Water Treatment Rule (LT2) would use their source water sampling site(s) that have been identified under that rule (71 FR 654, January 5, 2006 (USEPA, 2006a)). Systems subject to the Stage 1 Disinfectants and Disinfection Byproducts Rule (DBPR) would use their TOC source water sampling site(s) (63 FR 69390, December 16, 1998 (USEPA, 1998c)). TOC source water sampling site(s) were set under Stage 1 DBPR and remain unchanged under Stage 2 DBPR. If a system has two different source water sampling locations for LT2 and Stage 1 DBPR, the system would be permitted to select the sample point that best represents the definition of source water sample location(s) for UCMR.

      EPA proposes that PWSs monitor for HAAs only in the distribution system. If the system's treatment plant/water source is subject to sampling requirements under Sec. 141.622 (monitoring requirements for Stage 2 DBPR), the water systems must collect samples for the HAAs at the sampling locations identified under that rule (71 FR 388, January 4, 2006 (USEPA, 2006b)). If a treatment plant/water source is not subject to Stage 2 DBPR monitoring, then the water system must collect HAA distribution system samples at a location that represents the DSMRT. UCMR 4 HAA samples and HAA5 Stage 2 DBPR compliance monitoring samples may be collected by the PWS at the same time. However, in such cases, PWSs would be required to arrange for UCMR 4 HAA samples to be analyzed by a UCMR 4 approved laboratory using EPA Method 552.3 or 557 (compliance methods used for analysis of Stage 2 DBPR samples).

    3. Phased Sample Analysis for Microcystins

      EPA is proposing a phased sample analysis approach for microcystins to reduce analytical costs (i.e., PWSs must collect all required samples for each sampling event but not all samples may need to be analyzed). Two samples would be collected for ADDA ELISA (one source water intake sample and one EPTDS), and one sample would be collected for EPA Method 544 at the EPTDS. Initially, source water intake samples (collected by ``non-consecutive'' SW and GWUDI PWSs) would be analyzed for total microcystins as defined by an ADDA specific ELISA methodology. ADDA ELISA is a widely used screening assay that allows for the aggregate detection of numerous microcystin congeners; it does not allow for measurement of the individual congeners (USEPA, 2015c; Fischer et al., 2001; McElhiney and Lawton, 2005; Zeck et al., 2001). If the source water intake ELISA result is less than 0.3 micrograms per liter (mug/L) (i.e., the reporting limit for total microcystins), then the other collected samples (from the EPTDS) would not be analyzed for that sample event and only the source water result would be reported to EPA. If the ELISA result from the source water intake is greater than or equal to 0.3 mug/L, the result would be reported to EPA and the sample from the EPTDS would then also be analyzed for total microcystins by ELISA. ELISA analysis of the EPTDS sample would be the first step for consecutive systems. If the EPTDS ELISA result is less than 0.3 mug/L, then no additional analyses would be required for that particular sample event and the result would be reported to EPA. If the EPTDS ELISA result is greater than or equal to 0.3 mug/L, then that result would be reported to EPA and the other microcystin sample collected at the EPTDS would be analyzed using EPA Method 544 to identify and quantify six particular microcystin congeners and a related toxin, nodularin. Method 544 uses liquid chromatography with tandem mass spectrometry (LC/MS/MS) to quantify and speciate microcystin congeners at low concentrations. Using Method 544 to analyze EPTDS samples that tested positive for microcystins by ELISA is expected to help EPA and the states to establish the degree to which particular congener occurrence compares with total microcystin occurrence as measured by ADDA ELISA (USEPA, 2015c).

      This phased sample analysis approach for microcystins has the potential to achieve significant cost savings. A similar approach is not practical for cylindrospermopsin and anatoxin-a samples. Therefore, EPA proposes that cylindrospermopsin and anatoxin-a sampling be conducted simultaneously with the microcystins, twice a month for four consecutive months only at the EPTDS, and that the samples be analyzed using EPA Method 545.

    4. Representative Sampling

      As during past UCMRs and as described in Sec. 141.35(c)(3), the proposed rule would allow large GW systems that have multiple EPTDSs, with prior approval, to sample at representative sampling locations rather than at each EPTDS. Representative sampling plans approved under prior UCMRs will be recognized as valid for UCMR 4 and these systems must submit a copy of documentation from their state or EPA that approves their alternative sampling plan. Any new GW representative monitoring plans must be submitted to be reviewed by the state or EPA within 120 days from publication of the final rule. Once approved, these representative EPTDS locations, along with previously approved EPTDS locations from prior UCMRs, must be loaded into the Safe Drinking Water

      Page 76906

      Accession and Review System (SDWARS) by December 31, 2017.

    5. Summary

      With the exception of the increased sample frequency, phased sample analysis for microcystins, revised sampling locations and the compressed monitoring schedule, the approach to UCMR 4 Assessment Monitoring remains consistent with that established for UCMR 3.

      EPA invites comments regarding the cyanotoxin monitoring approach and the usefulness of collecting temperature and pH data (concurrently with the ELISA sample) at the source water intake, as well as designating source water type (e.g., lakes/reservoirs or flowing streams), as potential indicators of cyanotoxin occurrence. EPA also invites comments on the appropriateness of other potential cyanotoxin indicators, recognizing that the cost of any additional indicator monitoring would need to be weighed with consideration given to the likelihood of any other parameters serving as effective indicators.

      Finally, EPA recognizes the trade-off between PWS burden and occurrence-data representativeness, and has attempted to strike a reasonable balance in selecting the affected PWSs and establishing the monitoring frequency. The Agency welcomes comment on this particular point, including input regarding the appropriateness of collecting occurrence data from fewer PWSs. This could include employing the Screening Survey approach used in UCMR 3 or an alternative design. EPA requests that commenters suggesting alternatives describe how their proposed approach would be nationally representative of the frequency and level of contaminant occurrence.

  37. What are reporting requirements for UCMR 4?

    1. Data Elements

      EPA proposes the following changes to the reporting requirements listed in Table 1 of Sec. 141.35(e) to account for the UCMR 4 contaminants being proposed and the associated indicators. Additionally, EPA proposes to collect quality control information related to sample analysis. This information would further ensure that methods are followed as written, and would provide continuous quality assurance of data reported. EPA collected this information for small systems in previous UCMRs and found that doing so helps ensure that laboratories consistently follow the methods.

      Add Public Water System Name. New data element to be assigned once by the PWS.

      Add Public Water System Facility Name. New data element to be assigned once by the PWS for every facility identification code.

      Add Public Water System Facility Type. New data element to be assigned once by the PWS for every facility.

      Update Sampling Point Identification Code. Added ``source water'' as an example of applicable sampling locations.

      Add Sampling Point Name. New data element to be assigned once by the PWS for every sampling point identification code.

      Update Sample Point Type Code. Add source water (SR) to account for brominated HAA indicators and microcystin monitoring at the intake to the treatment plant.

      Update Disinfectant Type. Adding the following primary disinfectant/oxidation practices: Permanganate applied before SR sample location (PEMB) and after (PEMA), hydrogen peroxide applied before SR sample location (HPXB) and after (HPXA), and chlorine dioxide applied before SR sample location (CLDB) and after (CLDA).

      Add Treatment Information. New data element to capture treatment associated with the water being sampled.

      Add Disinfectant Residual Type. New data element to capture disinfectant residual type information associated with the water being sampled.

      Add Extraction Batch Identification Code. New data element to allow evaluation of quality control elements associated with extraction of samples in methods where extraction is required.

      Add Extraction Date. New data element identifying the date of sample extraction.

      Add Analysis Batch Identification Code. New data element to allow evaluation of quality control elements associated with analyzing samples.

      Add Analysis Date. New data element identifying the start date of sample analysis.

      Update Sample Analysis Type. The following elements are proposed as quality assurance measures:

      cir Continuing calibration check (CCC), an element that verifies the accuracy of method calibration;

      cir Internal standard (IS), an element that measures the relative response of contaminants;

      cir Laboratory fortified blank (LFB), an element that verifies method performance in the absence of a sample matrix;

      cir Laboratory reagent blank (LRB), an element that verifies the absence of interferences in the reagents and equipment;

      cir Quality control sample (QCS), an element that verifies the accuracy of the calibration standards;

      cir Quality HAA (QH), HAA sample collected and submitted for quality control; and,

      cir Surrogate standard (SUR), an element that assesses method performance for each extraction.

      Update Analytical Result--Value. Update to ``Analytical Result--Measured Value.'' The measured value is the analytical result for the contaminant.

      Add Additional Value. This element is used for quality control samples and is the amount of contaminant added to a QCS.

      Update Sample Event Code. Revise sample event codes to uniquely identify sampling events with specific codes for cyanotoxin and additional chemical monitoring.

    2. Duplicate Samples

      Currently, Sec. 141.40(a)(4)(ii)(F), requires EPA to randomly select a small percentage of small water systems to collect duplicate water samples for quality control purposes. Based on experience from previous UCMRs, this requirement did not provide significant useful information and EPA proposes to remove the requirement for the collection of duplicate samples from UCMR 4.

  38. What are Minimum Reporting Levels (MRLs) and how were they determined?

    The analyte minimum reporting level (MRL) is a quantitation level designed to be an estimate of the reporting level that is achievable, with 95% confidence, by a capable analyst/laboratory at least 75% of the time, using the prescribed method. Demonstration of the ability to reliably make quality measurements at or below the MRL is intended to ensure that high quality results are being reported by participating laboratories. MRLs are generally established as low as is reasonable (and are typically lower than the current health reference levels and health advisories), so that the occurrence data reported to EPA will support sound decision making, including those cases where new information might lead to lower health reference levels. EPA established the proposed MRL for each analyte/method by obtaining data from several laboratories performing ``lowest concentration minimum reporting level'' (LCMRL) studies. For further information on the LCMRL and MRL

    Page 76907

    process, see ``Technical Basis for the Lowest Concentration Minimum Reporting Level (LCMRL) Calculator'' (USEPA, 2010), available on the Internet at (http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods). EPA will consider raising MRLs if the Agency becomes aware of evidence that a proposed MRL is unattainable or impractical.

    I. How do laboratories become approved to conduct UCMR 4 analyses?

    The proposed rule would require EPA approval for all laboratories conducting analyses for UCMR 4. EPA anticipates following the traditional Agency approach to approving UCMR laboratories, which would require laboratories seeking approval to: (1) Provide EPA with data that demonstrate a successful completion of an initial demonstration of capability (IDC) as outlined in each method; (2) verify successful performance at or below the MRLs as specified in this action; (3) provide information about laboratory operating procedures; and (4) successfully participate in an EPA proficiency testing (PT) program for the analytes of interest. Audits of laboratories may be conducted by EPA prior to and/or following approval. The ``UCMR 4 Laboratory Approval Requirements and Information Document'' (USEPA, 2015j) will provide guidance on the EPA laboratory approval program and the specific method acceptance criteria.

    EPA may supply analytical reference standards for select analytes to participating/approved laboratories when reliable standards are not readily available through commercial sources.

    The structure of the proposed UCMR 4 laboratory approval program is the same as that employed in previous UCMRs, and would provide an assessment of the ability of laboratories to perform analyses using the methods listed in Sec. 141.40(a)(3), Table 1. The UCMR 4 laboratory approval process is designed to assess whether laboratories possess the required equipment and can meet laboratory-performance and data-

    reporting criteria described in this action. Laboratory participation in the UCMR laboratory approval program is voluntary. However, as in previous UCMRs and as proposed for UCMR 4, EPA would require PWSs to exclusively use laboratories that have been approved under the program. EPA expects to post a list of approved UCMR 4 laboratories to: http://www2.epa.gov/dwucmr. Laboratories are encouraged to apply for UCMR 4 approval as early as possible, as EPA anticipates that large PWSs scheduled for monitoring in the first year will be making arrangements for sample analyses soon after the final rule is published. The anticipated steps and requirements for the laboratory approval process are listed in the following paragraphs, steps 1 through 6.

    1. Request To Participate

      Laboratories interested in the UCMR 4 laboratory approval program would first email EPA at: UCMR_Sampling_Coordinator@epa.gov to request registration materials. EPA expects to accept such requests beginning December 11, 2015. EPA anticipates that the final opportunity for a laboratory to complete and submit the necessary registration information will be 60 days after final rule publication.

    2. Registration

      Laboratory applicants provide registration information that includes: laboratory name, mailing address, shipping address, contact name, phone number, email address and a list of the UCMR 4 methods for which the laboratory is seeking approval. This registration step provides EPA with the necessary contact information, and ensures that each laboratory receives a customized application package.

    3. Application Package

      Laboratories that wish to participate complete and return a customized application package that includes the following: IDC data, including precision, accuracy and results of MRL studies; information regarding analytical equipment and other materials; proof of current drinking water laboratory certification (for select compliance monitoring methods); and example chromatograms for each method under review.

      As a condition of receiving and maintaining approval, the laboratory is expected to confirm that it will post UCMR 4 monitoring results and quality control data that meet method criteria (on behalf of its PWS clients) to EPA's UCMR electronic data reporting system, SDWARS.

    4. EPA's Review of Application Package

      EPA will review the application packages and, if necessary, request follow-up information. Laboratories that successfully complete the application process become eligible to participate in the UCMR 4 PT program.

    5. Proficiency Testing

      A PT sample is a synthetic sample containing a concentration of an analyte or mixture of analytes that is known to EPA, but unknown to the laboratory. To be approved, a laboratory is expected to meet specific acceptance criteria for the analysis of a UCMR 4 PT sample(s) for each analyte in each method, for which the laboratory is seeking approval. EPA intends to offer up to four opportunities for a laboratory to successfully analyze UCMR 4 PT samples. Up to three of these studies will be conducted prior to the publication of the final rule, and at least one study will be conducted after publication of the final rule. This allows laboratories to complete their portion of the laboratory approval process prior to publication of the final rule and receive their approval immediately following the publication of the final rule. A laboratory is expected to pass one of the PT studies for each analytical method for which it is requesting approval, and will not be required to pass a PT study for a method it already passed in a previous UCMR 4 PT study. EPA does not expect to conduct additional PT studies after the start of system monitoring; however, laboratory audits will likely be ongoing throughout UCMR 4 implementation. Initial laboratory approval is expected to be contingent on successful completion of a PT study. Continued laboratory approval is contingent on successful completion of the audit process and satisfactorily meeting all the other stated conditions.

    6. Written EPA Approval

      After successfully completing the preceding steps 1 through 5, EPA expects to send each laboratory a letter listing the methods for which approval is pending (i.e., pending promulgation of the final rule if the PT studies have been conducted prior to that time), or for which approval is granted (if after promulgation of the final rule). Laboratories receiving pending approval are expected to be granted approval without further action following promulgation of the final rule if no changes have been made to the rule that impact the laboratory approval program. EPA expects to contact the laboratory if changes are made between the proposed and final rules that warrant additional action by the laboratory.

  39. What documents are being incorporated by reference?

    The following methods are being incorporated by reference into this section for UCMR 4 monitoring. All approved material except for the Standard Method Online, is available for inspection electronically at http://www.regulations.gov (Docket ID No. OW-2015-0218), or from the sources listed for each method. EPA has worked to make these methods and documents

    Page 76908

    reasonably available to interested parties. The versions of the EPA and non-EPA methods that may be used to support monitoring under this rule are as follows:

    1. Methods From the U.S. Environmental Protection Agency

      The following methods are from the U.S. Environmental Protection Agency, Water Docket, EPA/DC, EPA West, Room 3334, 1301 Constitution Avenue NW., Washington, DC 20004.

      (i) EPA Method 150.1 ``pH Electrometric, in Methods for Chemical Analysis of Water and Wastes,'' 1983, EPA/600/4-79/020. Available on the Internet at http://www.nemi.gov. This is an EPA method for measuring pH in water samples using a meter with a glass electrode and reference electrode or a combination electrode. The proposal includes measurement of pH as a potential indicator for cyanotoxins.

      (ii) EPA Method 150.2 ``pH, Continuous Monitoring (Electrometric), in Methods for Chemical Analysis of Water and Wastes,'' 1983, EPA/600/

      4-79/020. Available on the Internet at http://www.nemi.gov. This is an EPA method for measuring pH of in-line water samples using a continuous flow meter with a glass electrode and reference electrode or a combination electrode.

      (iii) EPA Method 200.8 ``Determination of Trace Elements in Waters and Wastes by Inductively Coupled Plasma--Mass Spectrometry,'' Revision 5.4, 1994. Available on the Internet at https://www.nemi.gov. This is an EPA method for the analysis of elements in water by ICP-MS and is proposed to measure germanium and manganese.

      (iv) EPA Method 300.0 ``Determination of Inorganic Anions by Ion Chromatography Samples,'' Revision 2.1, 1993. Available on the Internet at http://www.nemi.gov. This is an EPA method for the analysis of inorganic anions in water samples using ion chromatography (IC) with conductivity detection. The proposal includes measurement of bromide as a potential indicator for HAAs.

      (v) EPA Method 300.1 ``Determination of Inorganic Anions in Drinking Water by Ion Chromatography,'' Revision 1.0, 1997. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of inorganic anions in water samples using IC with conductivity detection.

      (vi) EPA Method 317.0 ``Determination of Inorganic Oxyhalide Disinfection By-Products in Drinking Water Using Ion Chromatography with the Addition of a Postcolumn Reagent for Trace Bromate Analysis,'' Revision 2.0, 2001, EPA 815-B-01-001. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of inorganic anions in water samples using IC with conductivity detection.

      (vii) EPA Method 326.0 ``Determination of Inorganic Oxyhalide Disinfection By-Products in Drinking Water Using Ion Chromatography Incorporating the Addition of a Suppressor Acidified Postcolumn Reagent for Trace Bromate Analysis,'' Revision 1.0, 2002, EPA 815-R-03-007. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of inorganic anions in water samples using IC with conductivity detection.

      (viii) EPA Method 415.3 ``Determination of Total Organic Carbon and Specific UV Absorbance at 254 nm in Source Water and Drinking Water,'' Revision 1.1, 2005, EPA/600/R-05/055. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods. This is an EPA method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

      (ix) EPA Method 415.3 ``Determination of Total Organic Carbon and Specific UV Absorbance at 254 nm in Source Water and Drinking Water,'' Revision 1.2, 2009, EPA/600/R-09/122.Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods. This is an EPA method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

      (x) EPA Method 525.3 ``Determination of Semivolatile Organic Chemicals in Drinking Water by Solid Phase Extraction and Capillary Column Gas Chromatography/Mass Spectrometry (GC/MS),'' Version 1.0, February 2012, EPA/600/R-12/010. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods. This is an EPA method for the analysis of semivolatile organic chemicals in drinking water using SPE and GC/MS and is proposed to measure nine pesticides (alpha-hexachlorocyclohexane, chlorpyrifos, dimethipin, ethoprop, oxyfluorfen, profenofos, tebuconazole, total cis- and trans- permethrin, and tribufos).

      (xi) EPA Method 530 ``Determination of Select Semivolatile Organic Chemicals in Drinking Water by Solid Phase Extraction and Gas Chromatography/Mass Spectrometry (GC/MS),'' Version 1.0, January 2015, EPA/600/R-14/442. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods. This is an EPA method for the analysis of semivolatile organic chemicals in drinking water using SPE and GC/MS and is proposed to measure butylated hydroxyanisole, o-toluidine, and quinoline.

      (xii) EPA Method 541 ``Determination of 1-Butanol, 1,4-Dioxane, 2-

      Methoxyethanol and 2-Propen-1-ol in Drinking Water by Solid Phase Extraction and Gas Chromatography/Mass Spectrometry,'' November 2015, EPA 815-R-15-011. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of selected alcohols and 1,4-dioxane in drinking water using SPE and GC/MS and is proposed to measure 1-

      butanol, 2-methoxyethanol and 2-propen-1-ol.

      (xiii) EPA Method 544 ``Determination of Microcystins and Nodularin in Drinking Water by Solid Phase Extraction and Liquid Chromatography/

      Tandem Mass Spectrometry (LC/MS/MS),'' Version 1.0, February 2015, EPA/

      600/R-14/474. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods. This is an EPA method for the analysis of selected cyanotoxins in drinking water using SPE and LC-MS/MS with electrospray ionization (ESI) and is proposed to measure six microcystins (microcystin-LA, microcystin-LF, microcystin-LR, microcystin-LY, microcystin-RR, and microcystin-YR) and nodularin.

      (xiv) EPA Method 545 ``Determination of Cylindrospermopsin and Anatoxin-a in Drinking Water by Liquid Chromatography Electrospray Ionization Tandem Mass Spectrometry (LC/ESI-MS/MS),'' April 2015, EPA 815-R-15-009. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of selected cyanotoxins in drinking water using LC-MS/MS with electrospray ionization (ESI) and is proposed to measure cylindrospermopsin and anatoxin-a.

      (xv) EPA Method 552.3 ``Determination of Haloacetic Acids and Dalapon in Drinking Water by Liquid-Liquid Microextraction, Derivatization,

      Page 76909

      and Gas Chromatography with Electron Capture Detection,'' Revision 1.0, July 2003, EPA 815-B-03-002. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of haloacetic acids and dalapon in drinking water using liquid-liquid microextraction, derivatization, and GC with electron capture detection (ECD) and is proposed to measure three HAA groups (HAA5, HAA6Br and HAA9).

      (xvi) EPA Method 557 ``Determination of Haloacetic Acids, Bromate, and Dalapon in Drinking Water by Ion Chromatography Electrospray Ionization Tandem Mass Spectrometry (IC-ESI-MS/MS),'' Version 1.0, September 2009, EPA 815-B-09-012. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods. This is an EPA method for the analysis of haloacetic acids, bromate, and dalapon in drinking water using IC-MS/MS with electrospray ionization (ESI) and is proposed to measure three HAA groups (HAA5, HAA6Br and HAA9).

    2. Methods From ``ASTM International''

      The following methods are from ``ASTM International'', 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959.

      (i) ASTM D1293-12 ``Standard Test Methods for pH of Water.'' Available for purchase on the Internet at http://www.astm.org/Standards/D1293.htm. This is an ASTM method for measuring pH in water samples using a meter and associated electrodes.

      (ii) ASTM D5673-10 ``Standard Test Method for Elements in Water by Inductively Coupled Plasma-Mass Spectrometry,'' approved August 1, 2010. Available for purchase on the Internet at http://www.astm.org/Standards/D5673.htm. This is an ASTM method for the analysis of elements in water by ICP-MS and is proposed to measure germanium and manganese.

      (iii) ASTM D6581-12 ``Standard Test Methods for Bromate, Bromide, Chlorate, and Chlorite in Drinking Water by Suppressed Ion Chromatography.'' Available for purchase on the Internet at http://www.astm.org/Standards/D6581.htm. This is an ASTM method for the analysis of inorganic anions in water samples using IC with conductivity detection. The proposal includes measurement of bromide as a potential indicator for HAAs.

    3. Methods From ``Standard Methods for the Examination of Water & Wastewater''

      The following methods are from ``Standard Methods for the Examination of Water & Wastewater'', 21st edition (2005), American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

      (i) SM 2550 ``Temperature.'' This is a Standard Method for temperature measurements using a thermometer (mercury). The proposal includes measurement of temperature as a potential indicator for cyanotoxins.

      (ii) SM 3125 ``Metals by Inductively Coupled Plasma/Mass Spectrometry.'' This is a Standard Method for the analysis of metals and metalloids in water by ICP-MS and is proposed for the analysis of germanium and manganese.

      (iii) SM 4500-H+ B ``pH Value in Water by Potentiometry Using a Standard Hydrogen Electrode.'' This is a Standard Method for measuring pH of water samples using a meter, standard hydrogen electrode, and reference electrode.

      (iv) SM 5310B ``The Determination of Total Organic Carbon by High-

      Temperature Combustion Method.'' This is a Standard Method for the analysis of TOC in water samples using a a conductivity detector or a nondispersive infrared detector.

      (v) SM 5310C ``Total organic carbon by Persulfate-UV or Heated-

      Persulfate Oxidation Method.'' This is a Standard Method for the analysis of TOC in water samples using conductivity detector or a nondispersive infrared detector.

      (vi) SM 5310D ``Total organic carbon by Wet-Oxidation Method.'' This is a Standard Method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

    4. Methods From ``Standard Methods Online''

      The following methods are from ``Standard Methods Online,'' available for purchase on the Internet at http://www.standardmethods.org.

      (i) SM 2550-10 ``Temperature.'' This is a Standard Method for temperature measurements using a thermometer (fluid filled or electronic).

      (ii) SM 3125-09 ``Metals by Inductively Coupled Plasma/Mass Spectrometry (Editorial revisions, 2011).'' This is a Standard Method for the analysis of metals and metalloids in water by ICP-MS and is proposed to measure germanium and manganese.

      (iii) SM 4500-H+ B-00 ``pH Value in Water by Potentiometry Using a Standard Hydrogen Electrode.'' This is a Standard Method for measuring pH in water samples using a meter, standard hydrogen electrode, and reference electrode.

      (iv) SM 5310B-00 ``The Determination of Total Organic Carbon by High-Temperature Combustion Method.'' This is a Standard Method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

      (v) SM 5310C-00 ``Total organic carbon by Persulfate-UV or Heated-

      Persulfate Oxidation Method.'' This is a Standard Method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

      (vi) SM 5310D-00 ``Total organic carbon by Wet-Oxidation Method.'' This is a Standard Method for the analysis of TOC in water samples using a conductivity detector or a nondispersive infrared detector.

    5. Method From ``Ohio EPA''

      The following methodology is from Ohio EPA, Columbus, OH.

      (i) ELISA SOP ``Ohio EPA Total (Extracellular and Intracellular) Microcystins--ADDA by ELISA Analytical Methodology,'' Version 2.0. January 2015, available on the Internet at http://www.epa.ohio.gov/Portals/28/documents/habs/HAB_Analytical_Methodology.pdf. This is an Ohio EPA method for the analysis of cyanotoxins (microcystins and nodularin) in drinking water using an ELISA technique. The proposal includes measurement of ``total microcystins'' using this technique.

  40. What is the states' role in the UCMR program?

    UCMR is a direct implementation rule (i.e., EPA has primary responsibility for its implementation) and state participation is voluntary. Under previous UCMRs, specific activities that individual states, tribes and territories agreed to carry out or assist with were identified and established exclusively through Partnership Agreements (PAs). Through PAs, states, tribes and territories can help EPA implement the UCMR program and help ensure that the UCMR data are of the highest quality possible to best support Agency decision making. Under UCMR 4, EPA expects to continue to use the PA process to determine and document the following: The process for review and revision of the SMPs; replacing and updating system information; review and approval of proposed ground water representative monitoring plans; notification and instructions for

    Page 76910

    systems; and compliance assistance. EPA recognizes that states/primacy agencies often have the best information about PWSs in their state and encourages states to partner.

    SMPs include tabular listings of the systems that EPA selected and the proposed schedule for their monitoring. Initial SMPs also typically include instructions to states for revising and/or correcting system information in the SMPs, including modifying the sampling schedules for small systems. EPA expects to incorporate revisions from states, resolve any outstanding questions and return the final SMPs to each state.

    L. What stakeholder meetings have been held in preparation for UCMR 4?

    EPA incorporates stakeholder involvement into each UCMR cycle. Specific to the development of UCMR 4, EPA held two public stakeholder meetings and is announcing a third in this proposal (see sections II.L and II.M). EPA held a meeting focused on drinking water methods for CCL contaminants on May 15, 2013, in Cincinnati, Ohio. Participants included representatives of state agencies, laboratories, PWSs, environmental organizations and drinking water associations. Meeting topics included an overview of the regulatory process (CCL, UCMR and Regulatory Determination) and drinking water methods under development, primarily for CCL contaminants (see USEPA, 2013 for presentation materials). EPA held a second stakeholder meeting on June 25, 2014, in Washington, DC. Attendees representing state agencies, tribes, laboratories, PWSs, environmental organizations and drinking water associations participated in the meeting via webinar and in person. Meeting topics included a status update on UCMR 3; UCMR 4 potential sampling design changes relative to UCMR 3; UCMR 4 candidate analytes and rationale; and the laboratory approval process (see USEPA, 2014 for meeting materials).

  41. How do I participate in the upcoming stakeholder meeting?

    EPA will hold the third public stakeholder meeting (via webinar) on January 13, 2016. Topics will include the proposed UCMR 4 monitoring requirements, analyte selection and rationale, analytical methods, the laboratory approval process and ground water representative monitoring plans.

    1. Webinar Participation

      Those who wish to participate in the public webinar must register in advance no later than 5:00 p.m., eastern time on January 10, 2016, https://attendee.gotowebinar.com/register/7326881974233959170. To ensure adequate time for public statements, individuals or organizations interested in making a statement should identify their interest when they register. We ask that only one person present on behalf of a group or organization, and that the presentation be limited to ten minutes. Any additional statements from attendees will be taken during the webinar if time permits; alternatively, official comments can be submitted to the docket. The number of webinar connections available for the meeting is limited and will be available on a first-

      come, first-served basis. Further details about registration and participation in the webinar can be found on EPA's Unregulated Contaminant Monitoring Program Meetings and Materials Web page at http://www2.epa.gov/dwucmr/unregulated-contaminant-monitoring-rule-ucmr-meetings-and-materials.

    2. Webinar Materials

      Meeting materials are expected to be sent by email to all registered attendees prior to the public webinar. EPA will post the materials on the Agency's Web site for persons who are unable to attend the webinar. Please note, these materials could be posted after the webinar.

  42. How did EPA consider Children's Environmental Health?

    Executive Order 13045 does not apply to UCMR 4, however, EPA's Policy on Evaluating Health Risks to Children is applicable (See III.G. Executive Order 13045). By monitoring for unregulated contaminants that may pose health risks via drinking water, UCMR furthers the protection of public health for all citizens, including children. EPA considered children's health risks during the proposed rule development process for UCMR 4, including the decision-making process for prioritizing candidate contaminants, and included a representative from EPA's Office of Children's Health Protection as a participant on the UCMR 4 workgroup.

    The objective of UCMR 4 is to collect nationally representative drinking water data on a set of unregulated contaminants. Wherever feasible, EPA collects occurrence data for contaminants at levels below current ``reference concentrations'' (e.g., health advisories and health reference levels). By setting reporting levels as low as we reasonably can, the Agency positions itself to better address updated risk information in the future, including that associated with unique risks to children. EPA requests comments regarding any further steps that may be taken to evaluate and address health risks to children within the scope of UCMR 4.

  43. How did EPA address Environmental Justice?

    EPA did not identify any disproportionately high or adverse human health or environmental effects on minority, low-income or indigenous populations in the process of developing the proposed rule for UCMR 4 (See III.J. Executive Order 12898). By seeking to identify unregulated contaminants that may pose health risks via drinking water from all PWSs, UCMR furthers the protection of public health for all citizens. EPA recognizes that unregulated contaminants in drinking water are of interest to all populations and structured the rulemaking process and implementation of the proposed UCMR 4 rule to allow for meaningful involvement and transparency. EPA organized public meetings/webinars to share information regarding the development of UCMR 4; coordinated with tribal governments; and convened a workgroup with representatives from the EPA Regions, EPA Program Offices, EPA's Office of Research and Development and several states.

    EPA proposes to continue to collect U.S. Postal Service Zip Codes for each PWS's service area, as collected under UCMR 3, to support an assessment of whether or not minority, low-income and/or indigenous-

    population communities are uniquely impacted by particular drinking water contaminants. EPA solicits comment on additional actions the Agency could take to further address environmental justice within the UCMR program. EPA welcomes, for example, comments regarding sampling and/or modeling approaches, and the feasibility and utility of applying these approaches to determine disproportionate impacts.

    III. Statutory and Executive Order Reviews

  44. Executive Order 12866: Regulatory Planning and Review and Executive Order 13563: Improving Regulation and Regulatory Review

    This action is not a significant regulatory action and was therefore not submitted to OMB.

  45. Paperwork Reduction Act (PRA)

    The information collection activities in this proposed rule have been submitted for approval to OMB under the PRA. The ICR document that the EPA prepared has been assigned EPA ICR number 2192.07. You can find a

    Page 76911

    copy of the ICR in the docket for this rule, and it is briefly summarized here.

    The information that EPA proposes to collect under this rule fulfills the statutory requirements of section 1445(a)(2) of SDWA, as amended in 1996. The data will describe the source of the water, location and test results for samples taken from PWSs. The information collected will support Agency decisions as to whether or not to regulate particular contaminants under SDWA. Reporting is mandatory. The data are not subject to confidentiality protection.

    The annual burden and cost estimates described in this section are based on the implementation assumptions described in section II.F. Respondents to UCMR 4 include 1,600 small PWSs (800 for cyanotoxin monitoring and a different set of 800 for monitoring the additional 20 chemicals), the ~4,292 large PWSs and the 56 states and primacy agencies (~5,948 total respondents). The frequency of response varies across respondents and years. System costs (particularly laboratory analytical costs) vary depending on the number of sampling locations. For cost estimates, EPA assumed that systems would conduct sampling evenly across March 2018 through November 2020, excluding December, January or February of each year, except for resampling purposes (i.e., one-third of the systems in each year of monitoring). Because the applicable ICR period is 2017-2019, one year of monitoring activity (i.e., 2020) is not captured in the ICR estimates; this will be addressed in a subsequent ICR renewal for UCMR 4.

    Small PWSs that are selected for UCMR 4 monitoring would sample an average of 6.7 times per PWS (i.e., number of responses per PWS) across the 3-year ICR period. The average burden per response for small PWSs is estimated to be 2.8 hours. Large PWSs (those serving 10,001 to 100,000 people) and very large PWSs (those serving more than 100,000 people) would sample and report an average of 11.4 and 14.1 times per PWS, respectively, across the 3-year ICR period. The average burden per response for large and very large PWSs is estimated at 6.1 and 9.9 hours, respectively. States are assumed to have an annual average burden of 366.5 hours related to coordination with EPA and PWSs. In aggregate, during the ICR period, the average response (e.g., responses from PWSs and states) is associated with a burden of 6.9 hours, with a labor plus non-labor cost of $1,705 per response.

    The annual average per-respondent burden hours and costs for the ICR period are: Small PWSs--6.2 hours, or $171, for labor; large PWSs--

    23.3 hours, or $682, for labor, and $6,047 for analytical costs; very large PWSs--46.5 hours, or $1,248, for labor, and $16,298 for analytical costs; and states--244.3 hours, or $11,598, for labor. Annual average burden and cost per respondent (including both systems and states) is estimated to be 23.4 hours, with a labor plus non-labor cost of $3,470 per respondent. Burden is defined at 5 CFR 1320.3(b).

    An agency may not conduct or sponsor, and a person is not required to respond to, a collection of information unless it displays a currently valid OMB control number. The OMB control numbers for EPA's rules in 40 CFR are listed in 40 CFR part 9.

    To comment on the Agency's need for this information, accuracy of the burden estimates or to provide suggested methods for minimizing respondent burden, reference the public docket for this rule, which includes the ICR. Submit any comments related to the ICR to EPA and OMB. See the ADDRESSES section at the beginning of this notice for where to submit comments to EPA and OMB. OMB is required to make a decision concerning the ICR between 30 and 60 days after December 11, 2015. Comments should be sent to OMB by January 11, 2016 for the comment to be appropriately considered. The final rule will contain responses to any OMB or public comments on the information collection requirements contained in this proposal.

  46. Regulatory Flexibility Act (RFA)

    For purposes of assessing the impacts of this proposed rule on small entities, EPA considered small entities to be PWSs serving 10,000 or fewer people, because this is the system size specified in SDWA as requiring special consideration with respect to small system flexibility. As required by the RFA, EPA proposed using this alternative definition in the FR, (63 FR 7606, February 13, 1998 (USEPA, 1998b)), requested public comment, consulted with the Small Business Administration and finalized the alternative definition in the Consumer Confidence Reports rulemaking, (63 FR 44512, August 19, 1998 (USEPA, 1998a)). As stated in that Final Rule, the alternative definition would be applied to future drinking water rules, including this rule.

    The evaluation of the overall impact on small systems, summarized in the preceding discussion, is further described as follows. EPA analyzed the impacts for privately-owned and publicly-owned water systems separately, due to the different economic characteristics of these ownership types, such as different rate structures and profit goals. However, for both publicly- and privately-owned systems, EPA used the ``revenue test,'' which compares annual system costs attributed to the rule to the system's annual revenues. EPA used median revenue data from the 2006 CWS Survey for public and private water systems. The revenue figures were updated to 2014 dollars, and to account for 3 percent inflation. EPA assumes that the distribution of the sample of participating small systems will reflect the proportions of publicly- and privately-owned systems in the national inventory. The estimated distribution of the representative sample, categorized by ownership type, source water and system size, is presented in Exhibit 6.

    Exhibit 6--Number of Publicly- and Privately-Owned Small Systems Subject to UCMR 4

    ----------------------------------------------------------------------------------------------------------------

    System size (number of people served) Publicly-owned Privately-owned Total \1\

    ----------------------------------------------------------------------------------------------------------------

    Ground Water

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................................... 21 64 85

    501 to 3,300..................................................... 161 62 223

    3,301 to 10,000.................................................. 179 41 220

    ----------------------------------------------

    Subtotal GW.................................................. 361 167 528

    ----------------------------------------------------------------------------------------------------------------

    Surface Water (and GWUDI)

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................................... 18 21 39

    Page 76912

    501 to 3,300..................................................... 241 86 327

    3,301 to 10,000.................................................. 548 158 706

    ----------------------------------------------

    Subtotal SW.................................................. 807 265 1,072

    ----------------------------------------------

    Total of Small Water Systems............................. 1,168 432 1,600

    ----------------------------------------------------------------------------------------------------------------

    \1\ PWS counts were adjusted to display as whole numbers in each size category.

    The basis for the proposed UCMR 4 RFA certification is as follows: For the 1,600 small water systems that would be affected, the average annual cost for complying with this rule represents no more than 0.8% of system revenues (the highest estimated percentage is for GW systems serving 500 or fewer people, at 0.8% of its median revenue). Exhibit 7 presents the yearly cost to small systems and to EPA for the small system sampling program, along with an illustration of system participation for each year of UCMR 4.

    Exhibit 7--Implementation of UCMR 4 at Small Systems

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    Cost description 2017 2018 2019 2020 2021 Total \1\

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    Costs to EPA for Small System Program (Assessment Monitoring)

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    $0 $5,971,948.............. $5,971,948.............. $5,971,948.............. $0 $17,915,845

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    Costs to Small Systems (Assessment Monitoring)

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    0 $273,210................ $273,210................ $273,210................ 0 $819,631

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    Total Costs to EPA and Small Systems for UCMR 4

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    0 $6,245,159.............. $6,245,159.............. $6,245,159.............. 0 $18,735,476

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    System Monitoring Activity Timeline \2\

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    Assessment Monitoring: Cyanotoxins.... ......... 1/3 PWSs Sample......... 1/3 PWSs Sample......... 1/3 PWSs Sample......... ......... 800

    Assessment Monitoring: 20 Additional ......... 1/3 PWSs Sample......... 1/3 PWSs Sample......... 1/3 PWSs Sample......... ......... 800

    Chemicals.

    --------------------------------------------------------------------------------------------------------------------------------------------------------

    \1\ Totals may not equal the sum of components due to rounding.

    \2\ Total number of systems is 1,600. No small system conducts Assessment Monitoring for both cyanotoxins and the 20 additional chemicals.

    PWS costs are attributed to the labor required for reading about UCMR 4 requirements, monitoring, reporting and record keeping. The estimated average annual burden across the 5-year UCMR 4 implementation period of 2017-2021 is 2.8 hours at $103 per small system. Average annual cost, in all cases, is less than 0.8% of system revenues. By assuming all costs for laboratory analyses, shipping and quality control for small entities, EPA incurs the entirety of the non-labor costs associated with UCMR 4 small system monitoring, or 96% of total small system testing costs. Exhibit 8 and Exhibit 9 present the estimated economic impacts in the form of a revenue test for publicly- and privately-owned systems.

    Exhibit 8--UCMR 4 Relative Cost Analysis for Small Publicly-Owned Systems

    2017-2021

    ----------------------------------------------------------------------------------------------------------------

    Average Average

    Annual number annual hours annual cost Revenue test

    System size (number of people served) of systems per system per system \2\ (%)

    impacted \1\ (2017-2021) (2017-2021)

    ----------------------------------------------------------------------------------------------------------------

    Ground Water Systems

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................. 4 1.6 $59 0.16

    501 to 3,300................................... 32 1.7 63 0.04

    3,301 to 10,000................................ 36 1.9 67 0.01

    ----------------------------------------------------------------------------------------------------------------

    Surface Water (and GWUDI) Systems

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................. 4 3.3 118 0.17

    501 to 3,300................................... 48 3.3 118 0.04

    Page 76913

    3,301 to 10,000................................ 109 3.4 123 0.01

    ----------------------------------------------------------------------------------------------------------------

    \1\ PWS counts were adjusted to display as whole numbers in each size category.

    \2\ The Revenue Test was used to evaluate the economic impact of an information collection on small government

    entities (e.g., publicly-owned systems); costs are presented as a percentage of median annual revenue in each

    size category.

    Exhibit 9--UCMR 4 Relative Cost Analysis for Small Privately-Owned Systems

    2017-2021

    ----------------------------------------------------------------------------------------------------------------

    Average Average

    Annual number annual hours annual cost Revenue test

    System size (number of people served) of systems per system per system \2\ (%)

    impacted \1\ (2017-2021) (2017-2021)

    ----------------------------------------------------------------------------------------------------------------

    Ground Water Systems

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................. 13 1.6 $59 0.81

    501 to 3,300................................... 12 1.7 63 0.05

    3,301 to 10,000................................ 8 1.9 67 0.01

    ----------------------------------------------------------------------------------------------------------------

    Surface Water (and GWUDI) Systems

    ----------------------------------------------------------------------------------------------------------------

    500 and under.................................. 4 3.3 118 0.29

    501 to 3,300................................... 17 3.3 118 0.04

    3,301 to 10,000................................ 32 3.4 123 0.01

    ----------------------------------------------------------------------------------------------------------------

    \1\ PWS counts were adjusted to display as whole numbers in each size category.

    \2\ The Revenue Test was used to evaluate the economic impact of an information collection on small government

    entities (e.g., privately-owned systems); costs are presented as a percentage of median annual revenue in each

    size category.

    The Agency has determined that 1,600 small PWSs (for Assessment Monitoring), or approximately 4.2% of all small systems, would experience an impact of no more than 0.8% of revenues; the remainder of small systems would not be impacted.

    Although this proposed rule will not have a significant economic impact on a substantial number of small entities, EPA has attempted to reduce this impact by assuming all costs for analyses of the samples and for shipping the samples from small systems to laboratories contracted by EPA to analyze UCMR 4 samples (the cost of shipping is now included in the cost of each analytical method). EPA has set aside $2.0 million each year from the Drinking Water State Revolving Fund (SRF) with its authority to use SRF monies for the purposes of implementing this provision of SDWA. Thus, the costs to these small systems will be limited to the labor associated with collecting a sample and preparing it for shipping.

    I certify that this action will not have a significant economic impact on a substantial number of small entities under the RFA. In making this determination, the impact of concern is any significant adverse economic impact on small entities. Although EPA has concluded that this action will have no significant net regulatory burden for directly regulated small entities, the Agency continues to be interested in the potential impacts of the proposed rule on small entities and welcomes comments on issues related to such impacts.

  47. Unfunded Mandates Reform Act (UMRA)

    This action does not contain an annual unfunded mandate of $100 million or more as described in UMRA, 2 U.S.C. 1531-1538, and does not significantly or uniquely affect small governments.

  48. Executive Order 13132: Federalism

    This action does not have federalism implications. It will not have substantial direct effects on the states, on the relationship between the national government and the states, or on the distribution of power and responsibilities among the various levels of government.

    Consistent with EPA policy to promote communications between EPA and state and local governments, EPA specifically solicits comment on the proposed rule from state and local officials.

  49. Executive Order 13175: Consultation and Coordination With Indian Tribal Governments

    This action will neither impose substantial direct compliance costs on federally recognized tribal governments, nor preempt tribal law. As described previously, this proposed rule requires monitoring by all large PWSs. Information in the SDWIS/Fed water system inventory indicates there are approximately 17 large tribal PWSs (ranging in size from 10,001 to 40,000 customers). EPA estimates the average annual cost to each of these large PWSs, over the 5-year rule period, to be $4,037. This cost is based on a labor component (associated with the collection of samples), and a non-labor component (associated with shipping and laboratory fees), and represents less than 1.2% of average revenue/

    sales for large PWSs. UCMR also requires monitoring by a nationally representative sample of small PWSs. EPA estimates that less than 2% of small tribal systems will be selected as a nationally representative sample for Assessment Monitoring. EPA estimates the average annual cost to small tribal systems over the 5-year rule period to be $103. Such cost is based on the labor associated with collecting a sample and preparing it for shipping

    Page 76914

    and represents less than 0.8% of average revenue/sales for small PWSs. All other small-PWS expenses (associated with shipping and laboratory fees) are paid by EPA.

    EPA consulted with tribal officials under the EPA Policy on Consultation and Coordination with Indian Tribes early in the process of developing this proposed rule to permit them to have meaningful and timely input into its development. A summary of that consultation is provided in the electronic docket listed in the ADDRESSES section at the beginning of this notice. EPA specifically solicits additional comment on this proposed rule from tribal officials.

  50. Executive Order 13045: Protection of Children From Environmental Health Risks and Safety Risks

    This action is not subject to Executive Order 13045 because it is not economically significant as defined in Executive Order 12866, and because EPA does not think the environmental health or safety risks addressed by this action present a disproportionate risk to children. This action's health and risk assessments are addressed in section II.N of the preamble.

  51. Executive Order 13211: Actions Concerning Regulations That Significantly Affect Energy Supply, Distribution or Use

    This action is not subject to Executive Order 13211, because it is not a significant regulatory action under Executive Order 12866.

    I. National Technology Transfer and Advancement Act and 1 CFR Part 51

    This action involves technical standards. EPA proposes to use methods developed by the Agency, three major voluntary consensus method organizations and the Ohio EPA to support UCMR 4 monitoring. The voluntary consensus method organizations are Standard Methods, Association of Analytical Communities International and ASTM International. EPA identified acceptable consensus method organization standards for the analysis of manganese and germanium. Additionally, EPA identified an Ohio EPA method for the analysis of total microcystins using ADDA by ELISA. EPA therefore proposes using a collection of analytical methods published by these parties for the UCMR 4 analytes. In addition, there are several consensus standards that are approved for compliance monitoring that will be available for use in the analysis of TOC and bromide, and for the measurement of temperature and pH. A summary of each method along with how the method specifically applies to UCMR 4 can be found in section II.J of the preamble.

    All of these standards are reasonably available for public use. The Agency methods are free for download on EPA's Web site. The methods in the Standard Method 21st edition are consensus standards, available for purchase from the publisher, and are commonly used by the drinking water community. The methods in the Standard Method Online are consensus standards, available for purchase from the publisher's Web site, and are commonly used by the drinking water community. The methods from ASTM International are consensus standards, are free for download from the publisher's Web site, and are commonly used by the drinking water community. The Ohio EPA method is free for download on their Web site and is increasingly being used by the drinking water community.

    EPA welcomes comments on this aspect of the proposed rulemaking; the Agency specifically invites the public to identify potentially-

    applicable voluntary consensus standards and explain why such standards should be used in this rule.

  52. Executive Order 12898: Federal Actions To Address Environmental Justice in Minority Populations and Low-Income Populations

    The EPA believes the human health or environmental risk addressed by this action will not have potential disproportionately high and adverse human health or environmental effects on minority, low-income or indigenous populations. The results of this evaluation are contained in section II.O of this preamble and an additional supporting document has been placed in the docket.

    IV. References

    ASDWA. 2013. Insufficient Resources for State Drinking Water Programs Threaten Public Health: An Analysis of State Drinking Water Programs' Resources and Needs. December 2013.

    ASTM. 2010. ASTM D5673-10--Standard Test Method for Elements in Water by Inductively Coupled Plasma-Mass Spectrometry. Approved August 1, 2010. Available for purchase on the Internet at http://www.astm.org/Standards/D5673.htm.

    ASTM. 2012a. ASTM D1293-12--Standard Test Methods for pH of Water. Available for purchase on the Internet at http://www.astm.org/Standards/D1293.htm.

    ASTM. 2012b. ASTM D6581-12--Standard Test Methods for Bromate, Bromide, Chlorate, and Chlorite in Drinking Water by Suppressed Ion Chromatography. Available for purchase on the Internet at http://www.astm.org/Standards/D6581.htm.

    Fischer, W.J., Garthwaite, I., Miles, C.O., Ross, K.M., Aggen, J.B., Chamberlin, A.R., Towers, N.R., Dietrich, D.R. 2001. Congener-

    Independent Immunoassay for Microcystins and Nodularins. Environmental Science & Technology, 35 (24), pp 4849-4856. Available for purchase on the Internet at http://dx.doi.org/10.1021/es011182f.

    Graham, J.L., Loftin, K.A., Ziegler, A.C., and Meyer, M.T. 2008. Guidelines for Design and Sampling for Cyanobacterial Toxin and Taste-and-Odor Studies in Lakes and Reservoirs: U.S. Geological Survey Scientific Investigations Report 2008-5038. Available on the Internet at http://pubs.usgs.gov/sir/2008/5038/.

    McElhiney, J., and Lawton, L.A. 2005. Detection of the Cyanobacterial Hepatotoxins Microcystins. Toxicology and Applied Pharmacology, 203 (3): 219-230. Available for purchase on the Internet at http://dx.doi.org/10.1016/j.taap.2004.06.002.

    Ohio EPA. 2015. Ohio EPA Total (Extracellular and Intracellular) Microcystins--ADDA by ELISA Analytical Methodology. Version 2.0. January 2015. Available on the Internet at http://www.epa.ohio.gov/Portals/28/documents/habs/HAB_Analytical_Methodology.pdf.

    Roberson, J.A., and Eaton, A. 2014. Retrospective Analysis of Mandated National Occurrence Monitoring and Regulatory Decisions. Journal of the American Water Works Association, 106 (3): E116-E128. Available on the Internet at http://dx.doi.org/10.5942/jawwa.2014.106.0040.

    Ryberg, K.R., and Gilliom, R.J. 2015. Trends in Pesticide Concentrations and Use for Major Rivers of the United States. Science of the Total Environment, 538: 431-444. Available for purchase on the Internet at http://dx.doi.org/10.1016/j.scitotenv.2015.06.095.

    SM Online. 2000a. SM 4500-H+ B-00--pH Value in Water by Potentiometry Using a Standard Hydrogen Electrode. Standard Methods Online. Available for purchase on the Internet at http://www.standardmethods.org.

    SM Online. 2000b. SM 5310B-00--The Determination of Total Organic Carbon by High-Temperature Combustion Method. Standard Methods Online. Available for purchase on the Internet at http://www.standardmethods.org.

    SM Online. 2000c. SM 5310C-00--Total organic carbon by Persulfate-UV or Heated-Persulfate Oxidation Method. Standard Methods Online. Available for purchase on the Internet at http://www.standardmethods.org.

    SM Online. 2000d. SM 5310D-00--Total organic carbon by Wet-Oxidation Method. Standard Methods Online. Available for purchase on the Internet at http://www.standardmethods.org.

    SM Online. 2009. SM 3125-09--Metals by Inductively Coupled Plasma/

    Mass Spectrometry (Editorial revisions, 2011). Standard Methods Online. Available for

    Page 76915

    purchase on the Internet at http://www.standardmethods.org.

    SM Online. 2010. SM 2550-10--Temperature. Standard Methods Online. Available for purchase on the Internet at http://www.standardmethods.org.

    SM. 2005a. SM 2550--Temperature. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    SM. 2005b. SM 3125--Metals by Inductively Coupled Plasma/Mass Spectrometry. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    SM. 2005c. SM 4500-H+ B--pH Value in Water by Potentiometry Using a Standard Hydrogen Electrode. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    SM. 2005d. SM 5310B--The Determination of Total Organic Carbon by High-Temperature Combustion Method. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    SM. 2005e. SM 5310C-00--Total Organic Carbon by Persulfate-UV or Heated-Persulfate Oxidation Method. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    SM. 2005f. SM 5310D--Total Organic Carbon by Wet-Oxidation Method. Standard Methods for the Examination of Water & Wastewater, 21st edition. American Public Health Association, 800 I Street NW., Washington, DC 20001-3710.

    USEPA. 1983a. EPA Method 150.1--pH Electrometric, in Methods for Chemical Analysis of Water and Wastes. EPA/600/4-79/020. Available on the Internet at http://www.nemi.gov.

    USEPA. 1983b. EPA Method 150.2--pH, Continuous Monitoring (Electrometric), in Methods for Chemical Analysis of Water and Wastes. EPA/600/4-79/020. Available on the Internet at http://www.nemi.gov.

    USEPA. 1993. EPA Method 300.0--Determination of Inorganic Anions by Ion Chromatography Samples. Revision 2.1. Available on the Internet at http://www.nemi.gov.

    USEPA. 1994. EPA Method 200.8--Determination of Trace Elements in Waters and Wastes by Inductively Coupled Plasma-Mass Spectrometry. Revision 5.4. Available on the Internet at https://www.nemi.gov/.

    USEPA. 1997. EPA Method 300.1--Determination of Inorganic Anions in Drinking Water by Ion Chromatography. Revision 1.0. 1997. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 1998a. National Primary Drinking Water Regulation: Consumer Confidence Reports; Final Rule. Federal Register. Vol. 63, No. 160, p. 44512, August 19, 1998.

    USEPA. 1998b. National Primary Drinking Water Regulations: Consumer Confidence Reports; Proposed Rule. Federal Register. Vol. 63, No. 30, p. 7606, February 13, 1998.

    USEPA. 1998c. National Primary Drinking Water Regulations: Disinfectants and Disinfection Byproducts; Final Rule. Federal Register. Vol. 63, No. 241, p. 69390, December 16, 1998.

    USEPA. 1999. Revisions to the Unregulated Contaminant Monitoring Regulation for Public Water Systems; Final Rule. Federal Register. Vol. 64, No. 180, p. 50556, September 17, 1999.

    USEPA. 2001a. EPA Method 317.0--Determination of Inorganic Oxyhalide Disinfection By-Products in Drinking Water Using Ion Chromatography with the Addition of a Postcolumn Reagent for Trace Bromate Analysis. Revision 2.0. EPA 815-B-01-001. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2001b. Statistical Design and Sample Selection for the Unregulated Contaminant Monitoring Regulation (1999). EPA 815-R-01-

    004, August 2001.

    USEPA. 2002. EPA Method 326.0--Determination of Inorganic Oxyhalide Disinfection By-Products in Drinking Water Using Ion Chromatography Incorporating the Addition of a Suppressor Acidified Postcolumn Reagent for Trace Bromate Analysis. Revision 1.0. EPA 815-R-03-007. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2003. EPA Method 552.3--Determination of Haloacetic Acids and Dalapon in Drinking Water by Liquid-Liquid Microextraction, Derivatization, and Gas Chromatography with Electron Capture Detection. Revision 1.0. EPA 815-B-03-002, July 2003. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2005. EPA Method 415.3--Determination of Total Organic Carbon and Specific UV Absorbance at 254 nm in Source Water and Drinking Water. Revision 1.1. EPA/600/R-05/055, February 2005. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods.

    USEPA. 2006a. National Primary Drinking Water Regulations: Long Term 2 Enhanced Surface Water Treatment Rule; Final Rule. Federal Register. Vol. 71, No. 3, p. 654, January 5, 2006.

    USEPA. 2006b. National Primary Drinking Water Regulations: Stage 2 Disinfectants and Disinfection Byproducts Rule; Final Rule. Federal Register. Vol. 71, No. 3, p. 388, January 4, 2006.

    USEPA. 2007. Unregulated Contaminant Monitoring Regulation (UCMR) for Public Water Systems Revisions. Federal Register. Vol. 72, No. 2, p. 368, January 4, 2007.

    USEPA. 2009a. EPA Method 415.3--Determination of Total Organic Carbon and Specific UV Absorbance at 254 nm in Source Water and Drinking Water. Revision 1.2. EPA/600/R-09/122, September 2009. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods.

    USEPA. 2009b. EPA Method 557--Determination of Haloacetic Acids, Bromate, and Dalapon in Drinking Water by Ion Chromatography Electrospray Ionization Tandem Mass Spectrometry (IC-ESI-MS/MS). Version 1.0. EPA 815-B-09-012, September 2009. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2010. Technical Basis for the Lowest Concentration Minimum Reporting Level (LCMRL) Calculator. EPA 815-R-11-001, December 2010. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2012a. EPA Method 525.3--Determination of Semivolatile Organic Chemicals in Drinking Water by Solid Phase Extraction and Capillary Column Gas Chromatography/Mass Spectrometry (GC/MS). Version 1.0. EPA/600/R-12/010, February 2012. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods.

    USEPA. 2012b. Request for Nominations of Drinking Water Contaminants for the Fourth Contaminant Candidate List. Federal Register. Vol. 77, No. 89, p. 27057, May 8, 2012.

    USEPA. 2012c. Revisions to the Unregulated Contaminant Monitoring Regulation (UCMR 3) for Public Water Systems; Final Rule. Federal Register. Vol. 77, No. 85, p. 26071, May 2, 2012.

    USEPA. 2013. Meetings and Materials for the Unregulated Contaminant Monitoring Program. Available on the Internet at http://www2.epa.gov/dwucmr/unregulated-contaminant-monitoring-rule-ucmr-meetings-and-materials.

    USEPA. 2014. Stakeholder Meeting Slides Regarding Revisions to the Unregulated Contaminant Monitoring Regulation.

    USEPA. 2015a. DRAFT Information Collection Request for the Unregulated Contaminant Monitoring Rule (UCMR 4). October 2015. EPA 815-B-15-003.

    USEPA. 2015b. Drinking Water Contaminant Candidate List 4--Draft. Federal Register, Vol. 80, No. 23, p. 6076, February 4, 2015.

    USEPA. 2015c. Drinking Water Health Advisory for the Cyanobacterial Microcystin Toxins. EPA 820-R-15-100, June 2015. Available on the Internet at http://www2.epa.gov/sites/production/files/2015-06/documents/microcystins-report-2015.pdf.

    USEPA. 2015d. EPA Method 530--Determination of Select Semivolatile Organic Chemicals in Drinking Water by

    Page 76916

    Solid Phase Extraction and Gas Chromatography/Mass Spectrometry (GC/

    MS). Version 1.0. EPA/600/R-14/442, January 2015. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods.

    USEPA. 2015e. EPA Method 541--Determination of 1-Butanol, 1,4-

    Dioxane, 2-Methoxyethanol and 2-Propen-1-ol in Drinking Water by Solid Phase Extraction and Gas Chromatography/Mass Spectrometry. EPA 815-R-15-011, November 2015. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2015f. EPA Method 544--Determination of Microcystins and Nodularin in Drinking Water by Solid Phase Extraction and Liquid Chromatography/Tandem Mass Spectrometry (LC/MS/MS). Version 1.0. EPA-600-R-14/474, February 2015. Available on the Internet at http://www2.epa.gov/water-research/epa-drinking-water-research-methods.

    USEPA. 2015g. EPA Method 545--Determination of Cylindrospermopsin and Anatoxin-a in Drinking Water by Liquid Chromatography Electrospray Ionization Tandem Mass Spectrometry (LC/ESI-MS/MS). EPA 815-R-15-009, April 2015. Available on the Internet at http://www2.epa.gov/dwanalyticalmethods/approved-drinking-water-analytical-methods.

    USEPA. 2015h. Proposed Revisions to CFR parts 141.35 and 141.40. EPA 815-B-15-006, November 2015. Available in EPA public docket (under Docket ID No. EPA-HQ-OW-2015-0218) on the Internet at http://www.regulations.gov.

    USEPA. 2015i. UCMR 4 Candidate Contaminants--Information Compendium. EPA 815-B-15-005, November 2015.

    USEPA. 2015j. UCMR 4 Laboratory Approval Requirements and Information Document. EPA 815-B-15-004, November 2015.

    USGS. 2014. Pesticides in Surface Waters: Seasonality of Pesticides in Surface Waters. U.S. Geological Survey Fact Sheet FS-039-97. Available on the Internet at http://water.usgs.gov/nawqa/pnsp/pubs/fs97039/sw5.html.

    Zeck, A., Weller, M.G., Bursill, D., Niessner, R. 2001. Generic Microcystin Immunoassay Based on Monoclonal Antibodies Against Adda. Analyst, 126: 2002-2007. Available for purchase on the Internet at http://dx.doi.org/10.1039/B105064H.

    List of Subjects in 40 CFR Part 141

    Environmental protection, Chemicals, Incorporation by reference, Indian-lands, Intergovernmental relations, Radiation protection, Reporting and recordkeeping requirements, Water supply.

    Dated: November 30, 2015.

    Gina McCarthy,

    Administrator.

    For the reasons set forth in the preamble, EPA proposes to amend 40 CFR part 141 as follows:

    PART 141--NATIONAL PRIMARY DRINKING WATER REGULATIONS

    0

    1. The authority citation for part 141 continues to read as follows:

      Authority: 42 U.S.C. 300f, 300g-1, 300g-2, 300g-3, 300g-4, 300g-

      5, 300g-6, 300j-4, 300j-9, and 300j-11.

      Subpart D--Reporting and Recordkeeping

      0

    2. In Sec. 141.35:

      0

      1. Revise the third sentence in paragraph (b)(1).

        0

      2. Revise the second and third sentences in paragraph (b)(2).

        0

      3. Remove ``October 1, 2012,'' and add in its place ``December 31, 2017,'' in paragraph (c)(1).

        0

      4. Revise the second and third sentences in paragraph (c)(2).

        0

      5. Revise the last sentence in paragraph (c)(3)(i).

        0

      6. Revise the fifth sentence in paragraph (c)(3)(ii).

        0

      7. Remove ``October 1, 2012,'' and add in its place ``WITHIN 120 DAYS FROM PUBLICATION OF THE FINAL RULE,'' in paragraph (c)(4).

        0

      8. Revise paragraphs (c)(5)(i), (c)(6) introductory text, (d)(2), and (e).

        The revisions and additions read as follows:

        Sec. 141.35 Reporting for unregulated contaminant monitoring results.

        * * * * *

        (b) * * *

        (1) * * * Information that must be submitted using EPA's electronic data reporting system must be submitted through: http://www2.epa.gov/dwucmr. * * *

        (2) * * * If you have received a letter from EPA or your State concerning your required monitoring and your system does not meet the applicability criteria for UCMR established in Sec. 141.40(a)(1) or (2), or if a change occurs at your system that may affect your requirements under UCMR as defined in Sec. 141.40(a)(3) through (5), you must mail or email a letter to EPA, as specified in paragraph (b)(1) of this section. The letter must be from your PWS Official and must include your PWS Identification (PWSID) Code along with an explanation as to why the UCMR requirements are not applicable to your PWS, or have changed for your PWS, along with the appropriate contact information. * * *

        (c) * * *

        (2) * * * You must provide your sampling location(s) and associate each source water location with its entry point location(s) by December 31, 2017, using EPA's electronic data reporting system. You must submit, verify or update the following information for each sampling location, or for each approved representative sampling location (as specified in paragraph (c)(3) of this section regarding representative sampling locations): PWSID Code; PWS Name; PWS Facility Identification Code; PWS Facility Name; PWS Facility Type; Water Source Type; Sampling Point Identification Code; Sampling Point Name; and Sampling Point Type Code; (as defined in Table 1 of paragraph (e) of this section).

        (3) * * *

        (i) * * * You must submit a copy of the existing alternate EPTDS sampling plan or your representative well proposal, as appropriate, DATE 120 DAYS AFTER PUBLICATION OF THE FINAL RULE, as specified in paragraph (b)(1) of this section.

        (ii) * * * You must submit the following information for each proposed representative sampling location: PWSID Code; PWS Name; PWS Facility Identification Code; PWS Facility Name; PWS Facility Type; Sampling Point Identification Code; and Sampling Point Name (as defined in Table 1, paragraph (e) of this section). * * *

        * * * * *

        (5) * * *

        (i) General rescheduling notification requirements. Large systems may change their monitoring schedules up to December 31, 2017, using EPA's electronic data reporting system, as specified in paragraph (b)(1) of this section. After this date has passed, if your PWS cannot sample according to your assigned sampling schedule (e.g., because of budget constraints, or if a sampling location will be closed during the scheduled month of monitoring), you must mail or email a letter to EPA, as specified in paragraph (b)(1) of this section, prior to the scheduled sampling date. You must include an explanation of why the samples cannot be taken according to the assigned schedule, and you must provide the alternative schedule you are requesting. You must not reschedule monitoring specifically to avoid sample collection during a suspected vulnerable period. You are subject to your assigned UCMR sampling schedule or the schedule that you revised on or before December 31, 2017, unless and until you receive a

        Page 76917

        letter from EPA specifying a new schedule.

        * * * * *

        (6) Reporting monitoring results. For UCMR samples, you must report all data elements specified in Table 1 of paragraph (e) of this section, using EPA's electronic data reporting system. You also must report any changes, relative to what is currently posted, made to data elements 1 through 9 to EPA, in writing, explaining the nature and purpose of the proposed change, as specified in paragraph (b)(1) of this section.

        * * * * *

        (d) * * *

        (2) Reporting sampling information. You must provide your sampling location(s) and associate each source water location with its entry point location(s) by December 31, 2017, using EPA's electronic data reporting system, as specified in paragraph (b)(1) of this section. If this information changes, you must report updates, including new sources and sampling locations that are put in use before or during the PWS' UCMR sampling period, to EPA's electronic data reporting system within 30 days of the change, as specified in paragraph (b)(1) of this section. You must record all data elements listed in Table 1 of paragraph (e) of this section on each sample form and sample bottle, as appropriate, provided to you by the UCMR Sampling Coordinator. You must send this information as specified in the instructions of your sampling kit, which will include the due date and return address. You must report any changes made in data elements 1 through 9 by mailing or emailing an explanation of the nature and purpose of the proposed change to EPA, as specified in paragraph (b)(1) of this section.

        (e) Data elements. Table 1 defines the data elements that must be provided for UCMR monitoring.

        Table 1--Unregulated Contaminant Monitoring Reporting Requirements

        ------------------------------------------------------------------------

        Data element Definition

        ------------------------------------------------------------------------

    3. Public Water System The code used to identify each PWS. The

      Identification (PWSID) Code. code begins with the standard 2-

      character postal State abbreviation or

      Region code; the remaining 7 numbers are

      unique to each PWS in the State. The

      same identification code must be used to

      represent the PWS identification for all

      current and future UCMR monitoring.

    4. Public Water System Name.. Unique name, assigned once by the PWS.

    5. Public Water System An identification code established by the

      Facility Identification Code. State or, at the State's discretion, by

      the PWS, following the format of a 5-

      digit number unique within each PWS for

      each applicable facility (i.e., for each

      source of water, treatment plant,

      distribution system, or any other

      facility associated with water treatment

      or delivery). The same identification

      code must be used to represent the

      facility for all current and future UCMR

      monitoring.

    6. Public Water System Unique name, assigned once by the PWS,

      Facility Name. for every facility ID (e.g., Treatment

      Plant).

    7. Public Water System That code that identifies that type of

      Facility Type. facility as either:

      CC = consecutive connection

      DS = distribution system

      IN = source water intake

      SS = sampling station

      TP = treatment plant

      OT = other

    8. Water Source Type......... The type of source water that supplies a

      water system facility. Systems must

      report one of the following codes for

      each sampling location:

      SW = surface water (to be reported for

      water facilities that are served all or

      in part by a surface water source at any

      time during the twelve-month period).

      GW = ground water (to be reported for

      water facilities that are served

      entirely by a ground water source).

      GU = ground water under the direct

      influence of surface water (to be

      reported for water facilities that are

      served all or in part by ground water

      under the direct influence of surface

      water at any time during the twelve-

      month sampling period), and are not

      served at all by surface water during

      this period.

    9. Sampling Point An identification code established by the

      Identification Code. State, or at the State's discretion, by

      the PWS, that uniquely identifies each

      sampling point. Each sampling code must

      be unique within each applicable

      facility, for each applicable sampling

      location (i.e., entry point to the

      distribution system, source water intake

      or distribution system sample at maximum

      residence time). The same identification

      code must be used to represent the

      sampling location for all current and

      future UCMR monitoring.

    10. Sampling Point Name....... Unique sample point name, assigned once

      by the PWS, for every sample point ID

      (e.g., Entry Point).

    11. Sampling Point Type Code.. A code that identifies the location of

      the sampling point as either:

      SR = source water taken from plant

      intake; untreated water entering the

      water treatment plant (i.e., a location

      prior to any treatment).

      EP = entry point to the distribution

      system.

      MR = distribution system sample at

      maximum residence time.

    12. Disinfectant Type........ All of the primary disinfectants/oxidants

      that have been added in the treatment

      plant to the water being sampled. To be

      reported by systems for each sampling

      point.

      PEMB = Permanganate (applied before SR

      sample location)

      PEMA = Permanganate (applied after SR

      sample location)

      HPXB = Hydrogen peroxide (applied before

      SR sample location)

      HPXA = Hydrogen peroxide (applied after

      SR sample location)

      CLGA = Gaseous chlorine

      CLOF = Offsite Generated Hypochlorite

      (stored as a liquid form)

      CLON = Onsite Generated Hypochlorite

      CAGC = Chloramine (formed from gaseous

      chlorine)

      CAOF = Chloramine (formed from offsite

      hypochlorite)

      CAON = Chloramine (formed from onsite

      hypochlorite)

      CLDB = Chlorine dioxide (applied before

      SR sample location)

      CLDA = Chlorine dioxide (applied after SR

      sample location)

      OZON = Ozone

      Page 76918

      ULVL = Ultraviolet light

      OTHD = All other types of disinfectant/

      oxidant

      NODU = No disinfectant/oxidant used

    13. Treatment Information.... Treatment information associated with the

      water being sampled.

      CON = Conventional (non-softening)

      SCO = Softening conventional

      RBF = River bank filtration

      PSD = Pre-sedimentation

      INF = In-line filtration

      DFL = Direct filtration

      PCF = Precoat filtration

      SSF = Slow sand filtration

      BIO = Biological filtration

      REC = Reactor clarification (e.g. solids

      contact clarification, slurry

      recirculation clarification,

      Aciflosupreg)

      SBC = Sludge blanket clarification (e.g.

      Pulsatorsupreg, Super

      Pulsatorsupreg, contact adsorption

      clarifiers, floc-blanket clarifiers)

      ADC = Adsorption clarification (contact

      adsorption clarification)

      UTR = Unfiltered treatment

      PAC = Application of powder activated

      carbon

      GAC = Granular activated carbon (not part

      of filters in CON, SCO, INF, DFL, or

      SSF)

      AIR = Air stripping (packed towers,

      diffused gas contactors)

      POB = Pre-oxidation/disinfection with

      chlorine (applied before SR sample

      location)

      POA = Pre-oxidation/disinfection with

      chlorine (applied after SR sample

      location)

      MFL = Membrane filtration

      IEX = Ionic exchange

      UVT = Ultraviolet light

      AOX = Advanced oxidation (ultraviolet

      light with hydrogen peroxide and/or

      ozone)

      DAF = Dissolved air floatation

      CWL = Clear well/finished water storage

      without aeration

      CWA = Clear well/finished water storage

      with aeration

      ADS = Aeration in distribution system

      (localized treatment)

      OTH = All other types of treatment

      NTU = No treatment used

    14. Disinfectant Residual Secondary disinfectant type added in the

      Type. distribution system for each finished

      water sample.

      CL2 = Chlorine (i.e., originating from

      addition of free chlorine only)

      CLM = Chloramines (originating from with

      addition of chlorine and ammonia or pre-

      formed chloramines)

      CAC = Chlorine and chloramines (if being

      mixed from chlorinated and chloraminated

      water)

      NOD = No disinfectant residual

    15. Sample Collection Date... The date the sample is collected,

      reported as 4-digit year, 2-digit month,

      and 2-digit day (YYYY/MM/DD).

    16. Sample Identification An alphanumeric value up to 30 characters

      Code. assigned by the laboratory to uniquely

      identify containers, or groups of

      containers, containing water samples

      collected at the same sampling location

      for the same sampling date.

    17. Contaminant.............. The unregulated contaminant for which the

      sample is being analyzed.

    18. Analytical Method Code... The identification code of the analytical

      method used.

    19. Extraction Batch Laboratory assigned extraction batch ID.

      Identification Code. Must be unique for each extraction batch

      within the laboratory for each method.

      For CCC samples report the Analysis

      Batch Identification Code as the value

      for this field. For methods without an

      extraction batch, leave this field null.

    20. Extraction Date.......... Date for the start of the extraction

      batch (YYYY/MM/DD). For methods without

      an extraction batch, leave this field

      null.

    21. Analysis Batch Laboratory assigned analysis batch ID.

      Identification Code. Must be unique for each analysis batch

      within the laboratory for each method.

    22. Analysis Date............ Date for the start of the analysis batch

      (YYYY/MM/DD).

    23. Sample Analysis Type..... The type of sample collected and/or

      prepared, as well as the fortification

      level. Permitted values include:

      CF = concentration fortified; the

      concentration of a known contaminant

      added to a field sample reported with

      sample analysis types LFSM, LFSMD, LFB,

      CCC and QCS.

      CCC = continuing calibration check; a

      calibration standard containing the

      contaminant, the internal standard, and

      surrogate analyzed to verify the

      existing calibration for those

      contaminants.

      FS = field sample; sample collected and

      submitted for analysis under this rule.

      IS = internal standard; a standard that

      measures the relative response of

      contaminants.

      LFB = laboratory fortified blank; an

      aliquot of reagent water fortified with

      known quantities of the contaminants and

      all preservation compounds.

      LRB = laboratory reagent blank; an

      aliquot of reagent water treated exactly

      as a field sample, including the

      addition of preservatives, internal

      standards, and surrogates to determine

      if interferences are present in the

      laboratory, reagents, or other

      equipment.

      LFSM = laboratory fortified sample

      matrix; a UCMR field sample with a known

      amount of the contaminant of interest

      and all preservation compounds added.

      LFSMD = laboratory fortified sample

      matrix duplicate; duplicate of the

      laboratory fortified sample matrix.

      QCS = quality control sample; a sample

      prepared with a source external to the

      one used for initial calibration and

      CCC. The QCS is used to check

      calibration standard integrity.

      QH = quality HAA; HAA sample collected

      and submitted for quality control

      purposes.

      SUR = surrogate standard; a standard that

      assesses method performance for each

      extraction.

    24. Analytical Results--Sign. A value indicating whether the sample

      analysis result was:

      Page 76919

      (

VLEX uses login cookies to provide you with a better browsing experience. If you click on 'Accept' or continue browsing this site we consider that you accept our cookie policy. ACCEPT